| Date |
Text |
| 2004-03-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03120934 |
| | ADD: 2275 PALM BEACH LAKES BLVD |
| | CONT: HALLMARK BUILDERS |
| | TEL: (561)512-5517 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) QUESTION# 1 FROM 1ST PLAN REVIEW: |
| | THE TYPES OF COMBUSTIBLE LIQUIDS PRO- |
| | VIDED FROM THE FIRST PLAN REVIEW MAY |
| | HAVE SOME DESCREPANCIES. PROVIDE THE MAN |
| | UFACTURES FLASH POINT AND BOILING POINTS |
| | FOR THE LIST PROVIDED. EXAMPLE CLEARCOAT |
| | LOOKS LIKE IT MAY BE A CLASS II WITHA |
| | BOILING POINT OF 104.INCLUDE THE BREAK |
| | DOWN FOR LACQUERS AND LACQUER THINNERS. |
| | ALSO PROVIDE THE MSDS SHEETS. ON MANY |
| | MSDS SHEETS THEY WILL REQUIRE A EYE WASH |
| | |
| | 2) COMMENT# 2 FROM 1ST REVIEW, 407.1.3.5 |
| | SPRAY BOOTHS SHALL BE PROTECTED BY AN |
| | AUTOMATIC SUPRESSION SYSTEM. A NOTE ON |
| | THE DRAWINGS DOESN'T MEET THE REQUIRE- |
| | MENTS OF THE CODE. |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | |
| | 3) ONCE WE RECEIVE THE FLASH POINT AND |
| | BOILING POINT OF THE LIQUIDS TO BE |
| | STORED AND THE METHOD OF STORAGE (IF |
| | RATED FIRE CABINETS WILL BE REQUIRED) |
| | IF REQUIRED,SUBMIT CUT SHEETS, THEN THE |
| | OCCUPANCY WILL BE ASSIGNED. |
| | EXAMPLE; CLEARCOAT ON THE ENTERNET THIS |
| | LIQUID IS INDICATED AS A CLASS II LIQUID |
| | WITH A FLASH POINT OF 105. |
| | THE SECOND CONCERN IS TO PROVIDE |
| | MSDS SHEETS FOR THESE CHEMICALS, SOME |
| | CHEMICALS REQUIRE A EYE WASH FOR 15 MIN. |
| | |
| | 4) THE NOTE INDICATING THE 2 HR RATING |
| | IS OK,BUT PROVIDE THE GA FILE DETAIL ON |
| | THE PLAN FOR THE INSPECTOR TO BE ABLE TO |
| | INSPECT BY. |
| | |
| | 5)NOTE 5 FROM 1ST REVIEW, HAS BEEN |
| | PARTIALLY IGNORED. |
| | 5A) THE FOAM TRIM CAN NOT BE USED IN THE |
| | FIRE DISTRICT. F102.7 ARCHITECTURAL TRIM |
| | ON BUILDINGS IN THE FIRE DISTRICT SHALL |
| | BE CONSTRUCTED OF NON-COMBUSTIBLE |
| | MATERIALS OR FIRE RETARDANT TREATED |
| | WOOD. |
| | 5B) THE USE OF PLYWOOD FOR WALLS HAS |
| | BEEN DELETED FROM SOME PAGES,S3,S5 STILL |
| | HAVEDETAILS WITH THE USE OF WOOD AS WELL |
| | AS THE 3 MEMBER GIRDER IS A VERTICAL |
| | WALL SECTION!!!!!! |
| | 5C) THE USE OF PLYWOOD HAS BEEN REMOVED |
| | FROM THE EXTERIOR TOWER WALL DIAPHRAM |
| | WHAT MATERIAL WILL MAKE THE WALL |
| | DIAPHRAM? |
| | 5D) PLANS INDICATE ROOF SHEATHING ABOVE |
| | THE 35'-0" ELEVATION, ENG TO PROVIDE |
| | ATTACHMENT AND SPACING, REMEMBER ROOF |
| | ZONE #3 EDGE ZONES, NEGATIVE PRESSURES. |
| | |
| | 7) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) GLAZED SWING DOORS |
| | B) GLAZED SWING DOORS W/ SIDELIGHTS |
| | C) GLAZED SWING DOORS W/ SIDELIGHTS & |
| | TRANSOMS |
| | D) MULLIONS, VERTICAL & HORIZONTAL |
| | E)WINDOWS |
| | F) STORM SHUTTERS IF IMPACT GLAZING IS |
| | NOT USED. |
| | G) LOUVERS |
| | H) EFIS- FOAM MOLDINGS |
| | I) ROOF ASSEMBLIES |
| | J) TRUSS ANCHORS |
| | |
| | 8) ***********IMPORTANT*************** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 9) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | PROVIDE PRODUCT TESTING REPORTS!!!!!!!!! |
| | |
| | 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | PROVIDE PRODUCT TESTING REPORTS!!!!!!! |
| | |
| | 11) COMMENT 16 FROM 1ST REVIEW: RETURN |
| | COMMENT SHEET INDICATES BOTTOM CHORD |
| | LIVE LOAD ADDED TO PLANS NO CLOUD OR |
| | DELTA INDICATING CHANGE? WHERE? |
| | |
| | 12) PLANS INDICATE THE USE OF SEMCO |
| | STRAPS, REMOVE FROM PLANS!!!!! OUT OF |
| | BUSSINSS SINCE 1999! NO STATE APPROVALS |
| | ARE AVAILABLE. |
| | TRUSS ANCHOR SCHEDULE REMOVE THE WORD |
| | "SUBSTITUTE" |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | |
| | 13) ON THE SOUND ADVISE BUILDING HOW |
| | WILL THE NICHE BE ACHIEVED? |
| | |
| | 14) ROOFS REQUIRE DRAINAGE, PROVIDE |
| | GUTTER SYSTEM THAT COMPLIES WITH SECTION |
| | 1503.4.3 SIZING & DISCHARGE. |
| | |
| | 15) 1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 16) A NEW NOTICE OF COMMENCEMENT MUST BE |
| | RECORDED. ONCE THE NOTICE OF COMMENCE- |
| | MENT IS RECORDED WORK MUST BE STARTED |
| | WITHIN 90 DAYS OR RERECORDED. |
| | |
| | 17)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |