| Plan Review Notes For Permit 03120934 |
| Permit Number |
03120934 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-07 00:00:00 | DENIED: | | | 1.CU-1 LOCATED ON THE ROOF SHALL | | | COMPLY WITH 2001 FBC 1511.7 FOR HEIGHT | | | REQUIREMENT BEWTEEN THE ROOF SURFACE & | | | THE BOTTOM OF THE SUPPORT RAIL (SEE | | | ATTACHED). | | | | | | 2.CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | 3.PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA FOR THE SPRAY/MIXING | | | BOOTH AND VENTILATION DETAILS WITH | | | PERMIT APPLLICATION.INDICATE DISTANCE | | | BETWEEN EXHAUST TERMINATION AND PROPERTY | | | LINES ADJACENT BUILDINGS AND FRESH AIR | | | INTAKES.SHOW COMPLIANCE WITH NFPA 33, | | | AND 2001 FBC(M) CHAPTER 5.SEE COMMENTS | | | BY FIRE DEPT. AND BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|