| Date |
Text |
| 2003-12-29 00:00:00 | 1) THIS LOCATION APPEARS TO BE LOCATED |
| | IN THE CITY FIRE LIMITS. PLEASE |
| | SEE APPENDIX F, LOCAL AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE. CERTAIN |
| | RESTRICTIONS APPLY. |
| | |
| | 2) SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR THE PREFAB BOOTH AND |
| | MIXING BOOTH. THE PAINT BOOTH SHALL |
| | BE EQUIPPED WITH FIRE SUPPRESSION |
| | EQUIPMENT. |
| | |
| | 3) A TWO-HOUR FIRE SEPARATION IS |
| | REQUIRED BETWEEN THE GARAGE AND OTHER |
| | PORTIONS OF THE BUILDING. DOORS |
| | WITHIN THIS WALL SHALL BE AT LEAST |
| | 1 1/2 FIRE RATED. |
| | |
| | 4) PLEASE INDICATE HOW FLAMMABLE |
| | OR COMBUSTIBLE LIQUIDS WILL BE STORED |
| | IN GARAGE. |
| | |
| | 5) BUILDING ADDRESS REQUIRED. A MINIMUM |
| | OF 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 6) DOOR SCHEDULE INDICATES NO RATED |
| | FIRE DOORS. |
| | |
| | 7) A MINIMUM OF THREE FEET CLEARANCE |
| | IS REQUIRED ALL THE WAY AROUND THE |
| | SPRAY BOOTH. THE SPRAY BOOTH IS TO |
| | BE PROPERLY GROUNDED, VENTED, AND |
| | FIRE SUPPRESSION PROTECTED. THE |
| | EXHAUST DUCT IS TO BE PROPER SIZE AND |
| | HEIGHT TO VENT FLAMMBLE OR COMBUSTIBLE |
| | LIQUIDS. |
| | |
| | 8) EXIT SIGNS ABOVE DOOR LEADING |
| | FROM RECEPTION AREA INTO GARAGE IS NOT |
| | NEEDED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |