Plan Review Notes
Plan Review Notes For Permit 03120908
Permit Number 03120908
Review Stop B
Sequence Number 4
Notes
Date Text
2004-03-03 00:00:00****CORRECTIONS****
 REVISION #1, 2ND REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A SEPARATE PERMIT IS REQUIRED FOR
 THE REPLACEMENT OF THE AWNING FABRIC.
  
 2.)PLEASE SUBMIT TEST DATA FOR THE
 IMPACT GLASS.THE TEST REPORTS
 SUBMITTED WERE FOR THE EXISTING DOORS
 (FRAMES WITH GLASS).TEST DATA FOR THE
 NEW GLASS ONLY MUST BE SUBMITTED.
  
 3.)SEE PREVIOUS LIST, ITEM #8. PROVIDE
 A VALUE FOR THE JOB.
  
 4.)NOTE - SPRINKLER PERMIT #04010771.