| 2004-01-27 00:00:00 | *****CORRECTIONS***** |
| | REVISION #1 |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A SEPARATE PERMIT IS REQUIRED FOR |
| | THE REPLACEMENT OF THE AWNING FABRIC. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM #3.ALSO |
| | SEE PLUMBING REVIEWER'S CORRECTIONS IN |
| | REGARDS TO BATHROOM PLUMBING FIXTURES. |
| | THESE ITEMS HAVE BEEN ADDRESSED ON |
| | PLUMBING PERMIT #04010301; MAKE THE |
| | DETAILS CONSISTENT ON THIS PLAN TO |
| | SHOW COMPLIANCE WITH FBC11. |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #8, THE |
| | DOOR SHOWN AT THE OFFICE BLOCKS THE |
| | EGRESS, FBC1012.1.4. |
| | |
| | 4.)PROVIDE THE TEST DATA FOR THE |
| | IMPACT GLASS. |
| | |
| | 5.)WHEELCHAIR TURNING SPACE REQUIRED |
| | IN THE KITCHEN, FBC11-4.2.3. |
| | |
| | 6.)THE KITCHEN SINK IS TO COMPLY WITH |
| | FBC11-4.24.2 (34" MAX HEIGHT), FBC |
| | 11-4.24.3 (KNEE CLEARANCE). |
| | |
| | 7.)THE ORIGINAL PERMIT APPLICATION IS |
| | NO LONGER IN THE PACKAGE.PLEASE |
| | PROVIDE. |
| | |
| | 8.)PROVIDE A VALUE FOR THE ENTIRE JOB. |
| | ORIGINAL VALUATION WAS BASED ON WALL |
| | FRAMING ONLY.THIS VALUATION SHOULD |
| | INCLUDE ALL WORK, INCLUDING TRADES. |
| | |
| | 9.)PROVIDE A TITLE BLOCK WITH LICENSE |
| | NUMBER AND SEAL FOR THE FIRST PAGE. |
| | |
| | 10.) FIRE SPRINKLER PLAN REQUIRED, FBC |
| | 104.3.1.1(5). |
| | |
| | 6.)THE SALES COUNTER IS TO COMPLY WITH |
| | FBC 11-7.2. |
| | |
| | 7.)HANDRAILS ARE TO COMPLY WITH |
| | FBC1608.2.1 AND FBC1007.5.3. |
| | |
| | 8.)SEE ATTACHED NOTICE IN REGARDS TO |
| | FS553.80(2)(B). |