Plan Review Notes
Plan Review Notes For Permit 03120908
Permit Number 03120908
Review Stop B
Sequence Number 3
Notes
Date Text
2004-01-27 00:00:00*****CORRECTIONS*****
 REVISION #1
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A SEPARATE PERMIT IS REQUIRED FOR
 THE REPLACEMENT OF THE AWNING FABRIC.
  
 2.)SEE PREVIOUS LIST, ITEM #3.ALSO
 SEE PLUMBING REVIEWER'S CORRECTIONS IN
 REGARDS TO BATHROOM PLUMBING FIXTURES.
 THESE ITEMS HAVE BEEN ADDRESSED ON
 PLUMBING PERMIT #04010301; MAKE THE
 DETAILS CONSISTENT ON THIS PLAN TO
 SHOW COMPLIANCE WITH FBC11.
  
 3.)SEE PREVIOUS LIST, ITEM #8, THE
 DOOR SHOWN AT THE OFFICE BLOCKS THE
 EGRESS, FBC1012.1.4.
  
 4.)PROVIDE THE TEST DATA FOR THE
 IMPACT GLASS.
  
 5.)WHEELCHAIR TURNING SPACE REQUIRED
 IN THE KITCHEN, FBC11-4.2.3.
  
 6.)THE KITCHEN SINK IS TO COMPLY WITH
 FBC11-4.24.2 (34" MAX HEIGHT), FBC
 11-4.24.3 (KNEE CLEARANCE).
  
 7.)THE ORIGINAL PERMIT APPLICATION IS
 NO LONGER IN THE PACKAGE.PLEASE
 PROVIDE.
  
 8.)PROVIDE A VALUE FOR THE ENTIRE JOB.
 ORIGINAL VALUATION WAS BASED ON WALL
 FRAMING ONLY.THIS VALUATION SHOULD
 INCLUDE ALL WORK, INCLUDING TRADES.
  
 9.)PROVIDE A TITLE BLOCK WITH LICENSE
 NUMBER AND SEAL FOR THE FIRST PAGE.
  
 10.) FIRE SPRINKLER PLAN REQUIRED, FBC
 104.3.1.1(5).
  
 6.)THE SALES COUNTER IS TO COMPLY WITH
 FBC 11-7.2.
  
 7.)HANDRAILS ARE TO COMPLY WITH
 FBC1608.2.1 AND FBC1007.5.3.
  
 8.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).