2004-01-24 00:00:00REVISION/DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SEE COMMENT #2 OF ELECTRICAL REVIEW
 CONCERNING METRO GROUP AND CERTIFICATES
 OF AUTHORIZATIONS PER 61G15-23.002 AND
 FS 471.023
 2) SHT A-3 ACCESSIBLE FIXTURE DETAILS:
 SHOW HEIGHT OF W/C 11-4.16.3, FLUSH CON-
 TROLS 11-4.16.5,-LAV HEIGHT AND
 CLEARANCES PER 11-4.19.2,-TOILET
 ROOM UNOBSTRUCTED TURNING SPACE COMPLY-
 ING WITH 11-4.2.3,-DRINKING FOUNTAIN
 SPOUT HEIGHT 11-4.15.2, CLEARANCES PER
 11-4.15.5, AND PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING PER
 11-4-1-3(10)(A),-KITCHENETTE SINK
 HEIGHT 11-4.24.2, KNEE CLEARANCE 11-4.24
 .3, DEPTH 11-4.24.4, CLEAR FLOOR SPACE
 11-4-24.5, EXPOSED PIPES AND SURFACES
 11-4.24.6 AND FAUCTES 11-4.24.7.
 3) A SANITARY RISER DIAGRAM AND A WATER
 RISER DIAGRAM ARE REQUIRED PER SECTION
 104.3.1.1
  
 REVIEW BY KEN STEVENS