2004-01-26 00:00:00DENIED:MECHANICAL PERMIT 04010560
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.DUCT SMOKE DETECTORS REQUIRED IN ALL
 SYSTEMS WITH THE DESIGN CAPACITY GREATER
 THAN 2,000 CFM.DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE SUPPLY AIR
 DUCT PER 2001 FBC(M) 606.2.1.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER NFPA 90A
 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.