| Plan Review Notes For Permit 03120908 |
| Permit Number |
03120908 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-26 00:00:00 | DENIED:MECHANICAL PERMIT 04010560 | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 403.3. | | | | | | 2.DUCT SMOKE DETECTORS REQUIRED IN ALL | | | SYSTEMS WITH THE DESIGN CAPACITY GREATER | | | THAN 2,000 CFM.DUCT SMOKE DETECTORS | | | SHALL BE INSTALLED IN THE SUPPLY AIR | | | DUCT PER 2001 FBC(M) 606.2.1. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | | 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|