| Plan Review Notes For Permit 03120908 |
| Permit Number |
03120908 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-16 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ 2000 EDITION NOT 1994. | | | | | | 2) NEW WHITE FABRIC AWNINGS ARE TO | | | BE FIRE RETARDANT. | | | | | | 3) THE PROPOSED STEPS SHALL HAVE | | | HANDRAILS WITHIN 30 " OF ALL PORTIONS | | | OF THE REQUIRED EGRESS WIDTH OF THE | | | STAIRS. | | | | | | 4) WHEN THE DRYWALL CEILING IS PAINTED, | | | CARE IS TO BE TAKEN NOT TO PAINT | | | EXISTING FIRE SPRINKLER HEADS. ANY | | | FIRE SPRINKLER HEADS THAT ARE PAINTED | | | SHALL BE REPLACED. | | | | | | 5) PLANS DO NOT CALL OUT NEW OR | | | EXISTING ILLUMINATED EXIT SIGNS, | | | EMERGENCY LIGHTING OR PORTABLE FIRE | | | EXTINGUISHERS. | | | | | | 6) NO FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS. | | | | | | 7) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|