| 2004-03-10 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE SIZE OF THE ATTIC ACCESS DOES NOT |
| | COMPLY WITH THE MINIMUM SPECIFIED BY |
| | FBC 2309.6. (20" X 36" MINIMUM) |
| | |
| | 3) ON SHEET A2 FBD IS INCORRECTLY |
| | SPECIFIED FOR FBC(FLORIDA BUILDING CODE) |
| | PLEASE CORRECT. |
| | |
| | 4) 1001.1.3/ 1005.4 ZERO LOT LINE |
| | EGRESS:WHEN ACCESS TO OR FROM A RE- |
| | QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| | ING OF A STRUCTURE TO THE PUBLIC WAY, |
| | REQUIRES TRANSVERSING A PROPERTY |
| | (ADJOINING LOT) THAT IS NOT PART OF THE |
| | ONE WHICH THE STRUCTURE IS LOCATED, AN |
| | EGRESS EASEMENT THROUGH THE ADJOINING |
| | PROPERTY IS REQUIRED AND SHALL BE RECORD |
| | ED IN THE COUNTY RECORDS. THIS EASEMENT |
| | SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| | ING SHALL BE PLACED WITHIN THE EASEMENT |
| | AREA WHICH WOULD BLOCK ACCESS TO THE |
| | EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| | FROM THE RESCUE OPENING TO THE PUBLIC |
| | WAY. NO LANDSCAPING, FENCES OR OTHER |
| | IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| | EASEMENT. SUBMIT A COPY OF THE RECORDED |
| | SUBDIVISION COVENANTS SPECIFYING THE |
| | ABOVE REQUIREMENTS. |
| | |
| | 5) THE FBC TABLE 600 CALCULATIONS FOR |
| | THE EXTERIOR WALL AT THE DINING ROOM AND |
| | DEN/STUDY ARE INCORRECT. SEE NOTES ON |
| | THE PLAN. ONLY 20% OF THE WALL AREA |
| | (64 SQFT) IS ALLOWED AS OPENINGS. PLEASE |
| | CORRECT. |
| | |
| | 6) SUBMIT 2 COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND UL LISTING |
| | INFORMATION FOR THE GAS BBQ AND HOOD. |
| | |
| | 7) INDICATE THAT THE 9,610# CAPACITY |
| | LISTED FOR STEEL COLUMN SC-1 IS FOR |
| | UPLIFT. |
| | |
| | 8) SPECIFY THE UPLIFT CAPACITY OF STEEL |
| | COLUMN SC-2. |
| | |
| | 9) ON SHEET S-2 THE ARROW SPECIFYING THE |
| | LOCATION FOR THE 4B CONNECTOR AT THE |
| | RIGHT SIDE OF THE ENTRY IS INDICATING |
| | THE WRONG PLACE. PLEASE CORRECT. |
| | |
| | 10) SPECIFY THE FASTENERS FOR CONNECTOR |
| | 4B ON S4. INDICATE THE TYPE, DIAMETER |
| | AND LENGTH/EMBED DEPTH. |
| | |
| | 11) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| | FOR THE FOLLOWING: |
| | - DOUBLE INSWING ENTRY DOORS |
| | - DOUBLE OUTSWING GLAZED DOORS WITH AND |
| | WITHOUT SIDELITES |
| | - SINGLE OUTSWING PANEL DOORS |
| | - SINGLE HUNG WINDOWS |
| | - FIXED GLASS WINDOWS (CIRCULAR,ARCHED, |
| | ETC.) |
| | - GLASS BLOCK (ONE HOUR FIRE RATED) |
| | - STRUCTURAL MULLIONS |
| | - OVERHEAD GARAGE DOORS |
| | - STORM PANELS |
| | |
| | 12) SUBMIT MANUFACTURER'S INSTALLATION |
| | SPECIFICATIONS AND LISTING FOR ONE HOUR |
| | FIRE RATED GLASS BLOCK. |
| | |
| | 13) SUBMIT AN INSTALLATION SCHEDULE AND |
| | KEY PLAN FOR THE STORM PANELS. SPECIFY |
| | THE MOUNT TYPE, ANCHOR TYPE AND SPACING |
| | ON THE INSTALLATION DRAWINGS. |
| | |
| | 14) A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR ROOFING. ROOFING CONTRACTOR HAD NOT |
| | SIGNED THE PERMIT AT TIME OF APPLICATION |
| | |
| | SUBMIT (2) COPIES OF ALL ITEMS REQUESTED |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |