2005-03-07 00:00:00* UNSAT *
  
  
 1)NOTE:PLEASE SEE RESPONSE LTR
 MENTIONS, ALL GFI'S FOR BATHS WERE ADDED
 FROM PREVIOUS TWO REVIEWS. PLEASE SEE
 LOWER BATH RM, NO GFI WAS INDICATED.
 PLEASE SEE PLAN HAVE BEEN REDLINED PER
 210.52D,210.8, IF EXISTING OR TO BE
 NEW??
  
 2)NOTE: PLEASE SEE SD'S ARE NOW ALL
 SHOWN AS EXISTING. OK.
  
 3)NOTE: PANEL SCHEDULE OCP/WIRE SIZES
 SHOWN. OK.
  
 4)NOTE: PLEASE SEE RESPONSE LTR MENTIONS
 LOAD CALCULATIONS WERE ATTACHED.?
 PLEASE SEE THESE WERE LOCATED IN PACKAGE
 WITH PRODUCT APPROVALS.
 PLEASE SEE 220.31B FOR LOAD CALCULATIONS
 FOR EXISTING SERVICES/ DWELLINGS.
 PLEASE SEE THERE ARE MANY ITEMS MIN
 REQUIRED UNDER 220.16,210.11
 TWO SMALL APPL? WASHER/LAUNDRY CIRCUIT
 ETC. 1500VA MIN.
 PLEASE ALSO SEE ALL SHEETS WHICH ARE
 SIGNED , DATED AND SEALED BY AN
 ARCHITECT REQUIRE A TITLE BLOCK WITH ALL
 INFORMATION AS REQUIRED UNDER FAC
 61G1-16.004, FS 481.219.
  
 5) NOTE: NOTE: PLEASE SEE 10KW AHU,
 SHOWN WITH 40A OCP.
 PLEASE SEE 424.3 FOR MIN OCP @125%. THIS
 IS A NOTE.
 PLEASE SEE MECH DETAIL MENTIONS OCP AT
 30A'S FOR 5KW UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  