| 2005-03-07 00:00:00 | * UNSAT * |
| | |
| | |
| | 1)NOTE:PLEASE SEE RESPONSE LTR |
| | MENTIONS, ALL GFI'S FOR BATHS WERE ADDED |
| | FROM PREVIOUS TWO REVIEWS. PLEASE SEE |
| | LOWER BATH RM, NO GFI WAS INDICATED. |
| | PLEASE SEE PLAN HAVE BEEN REDLINED PER |
| | 210.52D,210.8, IF EXISTING OR TO BE |
| | NEW?? |
| | |
| | 2)NOTE: PLEASE SEE SD'S ARE NOW ALL |
| | SHOWN AS EXISTING. OK. |
| | |
| | 3)NOTE: PANEL SCHEDULE OCP/WIRE SIZES |
| | SHOWN. OK. |
| | |
| | 4)NOTE: PLEASE SEE RESPONSE LTR MENTIONS |
| | LOAD CALCULATIONS WERE ATTACHED.? |
| | PLEASE SEE THESE WERE LOCATED IN PACKAGE |
| | WITH PRODUCT APPROVALS. |
| | PLEASE SEE 220.31B FOR LOAD CALCULATIONS |
| | FOR EXISTING SERVICES/ DWELLINGS. |
| | PLEASE SEE THERE ARE MANY ITEMS MIN |
| | REQUIRED UNDER 220.16,210.11 |
| | TWO SMALL APPL? WASHER/LAUNDRY CIRCUIT |
| | ETC. 1500VA MIN. |
| | PLEASE ALSO SEE ALL SHEETS WHICH ARE |
| | SIGNED , DATED AND SEALED BY AN |
| | ARCHITECT REQUIRE A TITLE BLOCK WITH ALL |
| | INFORMATION AS REQUIRED UNDER FAC |
| | 61G1-16.004, FS 481.219. |
| | |
| | 5) NOTE: NOTE: PLEASE SEE 10KW AHU, |
| | SHOWN WITH 40A OCP. |
| | PLEASE SEE 424.3 FOR MIN OCP @125%. THIS |
| | IS A NOTE. |
| | PLEASE SEE MECH DETAIL MENTIONS OCP AT |
| | 30A'S FOR 5KW UNIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |