| 2005-02-11 00:00:00 | *********** UNSAT ******************** |
| | |
| | 1)NOTE: PLEASE SEE RESPONSE LETTER |
| | MENTIONS MUCH OF THE ELECTRICAL WORK |
| | DONE UNDER PREVIOUS PERMITS, HOWEVER |
| | SINCE THOSE PLANS ETC ARE NO LONGER |
| | AVAILBLE AT THIS OFFICE, PLEASE SHOW ALL |
| | GFI'S AT THERE REQUIRED LOCATIONS PER |
| | 210.8, ALL BATHS, OUTSIDE? IF THESE ARE |
| | EXISTING DONE UNDER PREVIOUS PERMIT(S) |
| | PLEASE SHOW THESE LOCATIONS ON PLANS AND |
| | LABEL AS "E" FOR EXISTING. |
| | SD'S WERE ADDED AND NOTED IN LETTER AS |
| | EXISTING, PLEASE INDICATE BY "E" ON |
| | PLANS OR ADD NOTE FOR EXISTING. |
| | |
| | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER 220.31B, IF THIS WAS DONE UNDER |
| | PREVIOUS PERMIT WHICH INCLUDED ADDITION |
| | ETC, PLEASE INLCUDE THAT INFORMATION ON |
| | PLANS. PLEASE BE SURE LOAD CALCS DONE |
| | UNDER PREVIOUS PERMIT ARE PER 220.31B |
| | 220.3C1. |
| | |
| | 3)NOTE: PLEASE SEE PREVIOUS NOTES |
| | REQUESTED A PANEL SCHEDULE WITH MIN |
| | CIRCUITING REQUIRED. A PANEL SCHEDULE |
| | WAS SUBMITTED, HOWEVER, NO BRANCH |
| | CIRCUIT SIZES OR WIRE SIZES ARE SHOWN? |
| | PLEASE SHOW. |
| | |
| | 4)NOTE: IN REVIEW OF LETTER AND REMOVAL |
| | OF DETACHED BLDG WITH BEDRMS ETC, MANY |
| | OF THE COMMENTS FROM FIRST REVIEW ARE |
| | NOT RELEVANT AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |