Plan Review Notes
Plan Review Notes For Permit 03120888
Permit Number 03120888
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-11 00:00:00*********** UNSAT ********************
  
 1)NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS MUCH OF THE ELECTRICAL WORK
 DONE UNDER PREVIOUS PERMITS, HOWEVER
 SINCE THOSE PLANS ETC ARE NO LONGER
 AVAILBLE AT THIS OFFICE, PLEASE SHOW ALL
 GFI'S AT THERE REQUIRED LOCATIONS PER
 210.8, ALL BATHS, OUTSIDE? IF THESE ARE
 EXISTING DONE UNDER PREVIOUS PERMIT(S)
 PLEASE SHOW THESE LOCATIONS ON PLANS AND
 LABEL AS "E" FOR EXISTING.
 SD'S WERE ADDED AND NOTED IN LETTER AS
 EXISTING, PLEASE INDICATE BY "E" ON
 PLANS OR ADD NOTE FOR EXISTING.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220.31B, IF THIS WAS DONE UNDER
 PREVIOUS PERMIT WHICH INCLUDED ADDITION
 ETC, PLEASE INLCUDE THAT INFORMATION ON
 PLANS. PLEASE BE SURE LOAD CALCS DONE
 UNDER PREVIOUS PERMIT ARE PER 220.31B
 220.3C1.
  
 3)NOTE: PLEASE SEE PREVIOUS NOTES
 REQUESTED A PANEL SCHEDULE WITH MIN
 CIRCUITING REQUIRED. A PANEL SCHEDULE
 WAS SUBMITTED, HOWEVER, NO BRANCH
 CIRCUIT SIZES OR WIRE SIZES ARE SHOWN?
 PLEASE SHOW.
  
 4)NOTE: IN REVIEW OF LETTER AND REMOVAL
 OF DETACHED BLDG WITH BEDRMS ETC, MANY
 OF THE COMMENTS FROM FIRST REVIEW ARE
 NOT RELEVANT AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]