| Date |
Text |
| 2004-09-16 00:00:00 | *********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004. |
| | PLEASE INCLUDE ALL REQUIRED LICENSE # |
| | INFORMATION AS REQUIRED UNDER FS 481.219 |
| | THIS IS FOR ALL SHEETS AND TRADES, |
| | WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWERS. |
| | |
| | 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITIONS TO EXSITING DWELLINGS. |
| | PLEASE SHOW LOCATION OF SD'S AND GFI'S |
| | REQUIRED PER 2002 NEC. |
| | PLEASE ALSO SEE POSSIBLE EXCEPTIONS. |
| | |
| | 3)NOTE: PLEASE COMPLETE ELECTRICAL LIGHT |
| | -ING PLANS TO INCLUDE CONTROL OF LTS |
| | ETC. |
| | SHOWN ON REFLECTED CEILING PLAN ONLY. |
| | |
| | 4)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | SERVICE EQUIPMENT ON PLANS, INCLUDING |
| | MAIN DISC'S ETC. |
| | |
| | 5)NOTE: PLEASE SEE 250.32 FOR REQUIRED |
| | GROUNDING AT DETACHED BLDG. |
| | FOOTER STEEL AND CWP. |
| | PLEASE ALSO SEE MISSING CWP AT MAIN |
| | HOUSE. |
| | PLEASE SEE 250.66 FOR GROUNDING ELEC- |
| | -TRODE CONDUCTOR. #2. |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | |
| | 8)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) |
| | FOR NEW CIRCUITING BEING ADDED. |
| | |
| | 9)NOTE: PLEASE ALSO SHOW ANY NEW A/C |
| | EQUIPMENT BEING INSTALLED. |
| | |
| | 10)NOTE: PLEASE PROVIDE LOAD CALCULAT- |
| | -IONS PER 220.31B |
| | |
| | 11)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | 12)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 13)NOTE: PLANS SHOW ALL PHASES ON THIS |
| | PERMIT APPLICATION, YET SOMW SHOWN TO |
| | BE FUTURE? PLEASE SHOW/CLARIFY WORK |
| | UNDER THIS PERMIT. |
| | |
| | 14)NOTE: PLEASE SEE DEATACHED? STORAGE? |
| | PLEASE SEE 225.31, 250.32 FOR MISSING |
| | INFORMATION FOR THIS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |