2004-05-12 00:00:00PROVISO:
 PLAN SHEET M-1 INDICATES A FLEX DUCT
 PENETRATING A FIRE RESISTANCE RATED
 ASSEMBLY.PER 2001 603.5.5 FLEXIBLE
 DUCTS ARE PROHIBITED THROUGH A FIRE
 RATED ASSEMBLY. FIRE DAMPER IS NOT
 REQUIRED IF IT COMPLIES WITH SECTION
 607.1.3.
  