| 2004-05-12 00:00:00 | PROVISO: | | | PLAN SHEET M-1 INDICATES A FLEX DUCT | | | PENETRATING A FIRE RESISTANCE RATED | | | ASSEMBLY.PER 2001 603.5.5 FLEXIBLE | | | DUCTS ARE PROHIBITED THROUGH A FIRE | | | RATED ASSEMBLY. FIRE DAMPER IS NOT | | | REQUIRED IF IT COMPLIES WITH SECTION | | | 607.1.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|