2004-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, A2.5 & A5.2 PROVIDE
 DETAILS FOR ADAPTABILITY FOR ROOMS #210
 AND #235. RESPONSE NOTED, BUT DETAILS
 STILL NEEDED ARE 11-4.16.2 CLEAR FLOOR
 SPACE, 11-4.16.4 BACKING FOR GRAB BARS,
 11-4.19.3 CLEAR FLOOR SPACE, 11-4.21.3
 BACKING FOR SEAT, 11-4.21.4 BACKING FOR
 GRAB BARS, 11-4.21.5 CONTROL LOCATION,
 11-4.21.7 CURBS, AND 11-4.23.3 TURNING A
 AREA. - SEE COMMENT #2 FROM PREVIOUS RE-
 VIEW
 2) THIS IS THE THIRD REJECTION AND A 4
 TIMES THE FEE MAY BE APPLIED FOR PLAN
 REVIEW PER FS 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]