2004-04-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST
 CONT:SHAWE-AGER CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM FIRST REVIEW:
 SHEET A2.1 SHOWS THE RECONFIGURATION OF
 THE FRONT ENTRY STAIR.
 1006.1.1 EXIT STAIRWAYS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANCE CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2AND TABLE 705.1.2.
  
 THE ISSUE NOT BEING ADDRESSED ON THE
 FRONT EXIT STAIRWAY FROM PREVIOUS
 REVIEWS IS THERE ARE (2) REQUIRED MEANS
 OF EGRESS, THE STAIRWAY SHAFT OR STAIR
 ENCLOSURE,(EXIT) 1006.1.4 THERE SHALL
 BENO ENCLOSED USABLE SPACE WITHIN AN
 EXIT ENCLOSURE. 1006.1.3 A STAIRWELL
 ENCLOS- URE SHALL NOT BE USED FOR ANY
 OTHER PUR-POSE OTHER THAN A MEANS OF
 EGRESS.
 OPENINGS IN EXIT ENCLOSURES OTHER THAN
 UNEXPOSED EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR THE EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY
 OCCUPIABLE OR HABITABLE ROOMS AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 2) COMMENT# 4 FROM 1ST REVIEW:
 PRIVATE BATHROOMS, 11-4.1.3(11) PRIVATE
 BATHROOMS ARE TO BE ADAPTABLE. THIS
 WILL MEAN TO BE ADAPTABLE THE 5'-0"
 TURNING RADIUS IS IN AFFECT, BATHROOM
 235 APPEARS TO MAKE THIS REQUIREMENT
 INDICATE THE 5'-0" CLEAR TURNING RADIUS
 FOR BATHROOM 210. PROVIDE THE REQUIRED
 BACKING FOR AN ADAPTABLE BATHROOM
 (11-4.16.4) BACKING FOR GRAB BARS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026