Plan Review Notes
Plan Review Notes For Permit 03120833
Permit Number 03120833
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13.
 ROOM #235 SHALL BE ACCESSIBLE. PROVIDE
 DETAIL FOR 11-4.16 W/C'S, (SEE FIGS. 28
 & 29), 11-4.19 LAVS, (SEE FIGS. 31, & 32
 ), 11-4.21 SHOWERS, (SEE FIGS. 35, 36, &
 37), AND 11-4.23 SHOWER ROOMS. ALSO SHOW
 ALL SUBSECTIONS FOR EACH SECTION. 11-4.3
 .1(11) - RESPONSE NOTED, BUT BATHROOM #
 235 IS NOT ADJACENT TO OFFICE #208.
 OFFICES #234 & #236 ARE ADJACENT TO THIS
 BATHROOM AND ONLY PRIVATE BATHROOMS OF
 ONE OFFICE SHALL BE ADAPTABLE.
 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9.
 ROOM #210 SHALL BE ADAPTABLE. PROVIDE
 DETAILS SHOWING BACKING FOR GRAB BARS,
 CLEAR FLOOR SPACE, TURNING AREA, SHOWER
 CONTROLS, CURB, BACKING FOR SHOWER GRAB
 BARS, ECT. SECTIONS 11-4.1.3(11), 11-4.2
 1 (FIGS 35, 36, 37). - RESPONSE NOTED,
 BUT BATHROOM #210 IS ADJACENT TO OFFICE
 #208 AND CAN BE ADAPTABLE BUT DETAILS
 ARE REQUIRED.
 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4) THESE ARE COMMENTS FROM FIRST REVIEW
 THAT ARE BEING REQUIRED FOR THE SECOND
 REVIEW. SEE ATTACHED SHEET CONCERNING
 FS 533.80(2)(B) DESIGN PROFESSIONAL DOC-
 UMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]