| 2004-02-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13. |
| | ROOM #235 SHALL BE ACCESSIBLE. PROVIDE |
| | DETAIL FOR 11-4.16 W/C'S, (SEE FIGS. 28 |
| | & 29), 11-4.19 LAVS, (SEE FIGS. 31, & 32 |
| | ), 11-4.21 SHOWERS, (SEE FIGS. 35, 36, & |
| | 37), AND 11-4.23 SHOWER ROOMS. ALSO SHOW |
| | ALL SUBSECTIONS FOR EACH SECTION. 11-4.3 |
| | .1(11) - RESPONSE NOTED, BUT BATHROOM # |
| | 235 IS NOT ADJACENT TO OFFICE #208. |
| | OFFICES #234 & #236 ARE ADJACENT TO THIS |
| | BATHROOM AND ONLY PRIVATE BATHROOMS OF |
| | ONE OFFICE SHALL BE ADAPTABLE. |
| | 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9. |
| | ROOM #210 SHALL BE ADAPTABLE. PROVIDE |
| | DETAILS SHOWING BACKING FOR GRAB BARS, |
| | CLEAR FLOOR SPACE, TURNING AREA, SHOWER |
| | CONTROLS, CURB, BACKING FOR SHOWER GRAB |
| | BARS, ECT. SECTIONS 11-4.1.3(11), 11-4.2 |
| | 1 (FIGS 35, 36, 37). - RESPONSE NOTED, |
| | BUT BATHROOM #210 IS ADJACENT TO OFFICE |
| | #208 AND CAN BE ADAPTABLE BUT DETAILS |
| | ARE REQUIRED. |
| | 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 4) THESE ARE COMMENTS FROM FIRST REVIEW |
| | THAT ARE BEING REQUIRED FOR THE SECOND |
| | REVIEW. SEE ATTACHED SHEET CONCERNING |
| | FS 533.80(2)(B) DESIGN PROFESSIONAL DOC- |
| | UMENTS. |
| | |