Date Text
2004-03-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST
 CONT: RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM FIRST REVIEW:
 SHEET A-2.1 SHOWS A RECONFIGURATION OF
 THE FRONT ENTRY STAIR. THE 2ND FLOOR
 DEMO SHEET ALSO INDICATES A DOOR
 REMOVED FROM HALLWAY 228. THIS RECONFIG-
 URATION WITH RECEPTION AREA ELIMINATES
 THE 1HR RATING OF THE "STAIRWELL SHAFT".
 1006.1.1 EXIT STAIRWAYS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANT CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2 AND TABLE 705.1.2.
 TABLE 705.1.2 REQUIRES A 1HR RATED WALL
 AND 1 HR OPENING PROTECTIVES.
 705.1.3.41HR DOORS ARE TO BE USED IN
 STAIRWAYS. AVERAGE TEMP RISE DEVELOPED
 ON THE UNEXPOSED SIDE SHALL NOT EXCEED
 450 DEGREES F AT THE END OF 30 MINUTES
 OF STANDARD FIRE TEST EXPOSURE.
 TABLE 705.1.3.6
 WINDOWS IN SHAFTS, 705.2.3.5 OPENINGS
 IN SHAFT ENCLOSURES SHALLBE PERMITTED
 WHEN LIMITED TO THOSE NECESSARY FOR THE
 PURPOSE OF THE SHAFT. PERMITTED OPENINGS
 INSHAFT ENCLOSURES SHALL BE PROTECTED
 WITH OPENING PROTECTIVES HAVING A FIRE
 RESISTANCE IN ACORDANCE WITH 705.1.2.
 WINDOWS 1HR SEE TABLE 705.1.3.6 FOR
 WIRED GLASS PANELS USE 1HR RATING SIZE
 MAX100 SQ IN, 33"X12".
  
 705.2.2 DOES HAVE AN EXCEPTION TO THE
 SHAFT ENCLOSURE REQUIREMENT 705.2.2(2)
 BUT"ALL 6 REQUIREMENTS MUST BE MET",
 (1) IT IS A PART OF A MEANS OF EGRESS.
 PLANS ALSO INDICATE THAT (2) MEANS OF
 EGRESS ARE REQUIRED AS DOES 1004.1.4.
 THE SECOND ISSUE IS 1006.1.4 THERE
 SHALL BE NO ENCLOSED USABLE SPACE WITHIN
 AN EXIT ENCLOSURE. THERE MUST BE SEPERA-
 TION (1HR) BETWEEN THE ENCLOSED STAIR
 AND LOBBY OR SITTING ROOM! REVISE INDI-
 CATING RATED DOORS WINDOWS USAGE AS WELL
 AS PENETRATIONS INTO AND THROUGH A
 STAIRWELL ENCLOSURE 1006.1.3.1.
  
 2) NOTE# 3 FROM 1ST REVIEW:
 CORRECT, RAMPS 6" OR LESS DO NOT NEED TO
 MEET THE HANDRAIL REGULATIONS BUT THE
 SLOPE AND LANDING REQUIREMENTS OF:
 11.4.8.2 SLOPE & RISE
 11.4.8.4(2) LANDINGS **SEE BOTTOM LAND-
 ING 72"X36" MINIMUM.11-4.3.3 MINIMUM
 WIDTH OF AN ACCESSIBLE ROUTE IS 36".
  
 3) COMMENT# 4 FROM 1ST REVIEW:
 PRIVATE BATHROOMS, 11-4.1.3(11)
 PRIVATE BATHROOMS SHALL BE ADAPTABLE.
 TO BE ADAPTABLE THE SIZE REGULATIONS ARE
 IN AFFECT, AND BACKING REQUIRED. THESE
 REQUIREMENTS AFFECT ROOMS 210 & 235.
  
 4) COMMENT# 7 FROM 1ST REVIEW:
 WILL NEED TO APPLY FOR VARIANCE TO THE B
 OARD OF AJUSTMENT & APPEAL FOR VARIANCE
 TO USE DELUGE CURTIAN.
 THE VARIANCE SHOULD BE FOR A TYPE V
 BUILDING 0-3' FROM PROPERTY LINE REQUIR-
 ING THREE HR WALLS (ZERO % OPENINGS) TO
 ALLOW OPENINGS AT WHAT PERCENT? THE
 WATER CURTAIN SHOULD BE DESIGNED AS THE
 EQUAVALENT FOR A 3HR WALLAS PER NFPA 13
 WATER CURTAIN 5-13.4.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) IMPACT FIXED WINDOWS
 *********IMPORTANT**************
 *********IMPORTANT**************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026