| Date |
Text |
| 2004-01-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13. |
| | ROOM #235 SHALL BE ACCESSIBLE. PROVIDE |
| | DETAIL FOR 11-4.16 WATER CLOSETS, (SEE |
| | FIGS. 28 & 29), 11-4.19 LAVS, (SEE FIGS. |
| | 31 & 32), 11-4.21 SHOWERS, (SEE FIGS. 35 |
| | 36, & 37), AND 11-4.23 SHOWER ROOMS. |
| | ALSO SHOW ALL SUBSECTIONS FOR EACH SECT- |
| | ION. 11-4.3.1(11). |
| | 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9. |
| | ROOM #210 SHALL BE ADAPTABLE. PROVIDE |
| | DETAIL SHOWING BACKING FOR GRAB BARS, |
| | CLEAR FLOOR SPACE, TURNING AREA, LAV |
| | HEIGHT, OPENING FOR WATER CLOSET, SHOWER |
| | CONTROLS, CURB, BACKING FOR SHOWER GRAB |
| | BARS ECT. 11-4.1.3(11). |
| | 3) SHTS A2.1, A2.2, & A5.2 DETAIL #11. |
| | BREAK ROOM SINK SHALL COMPLY WITH SECT- |
| | ION 11-4.24 AND ALL SUBSECTIONS. PROVIDE |
| | A DETAIL. |
| | 4) SHT P-1 WATER ISOMETRIC AT DRINKING |
| | FOUNTAIN. AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE FROM DIAGRAM. |
| | 5) SHT P-1 SUBMIT WATER & SANITARY ISO- |
| | METRICS FOR BREAK ROOM SINK. SECTION |
| | 104.3.1.1. WATER HAMMER ARRESTOR REQUIR- |
| | ED FOR DISHWASHER. SECTION 604.9 |
| | 6) SHT P-1 PLUMBING NOTES: #12 AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE REF- |
| | ERENCE. |
| | 7) SHT P-2 FOLLOWING INFORMATION REQUIR- |
| | ED FOR APPLICATION FOR GAS PERMIT. |
| | SEPARATE PERMIT REQUIRED FOR GAS. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | D. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |