Plan Review Notes
Plan Review Notes For Permit 03120833
Permit Number 03120833
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13.
 ROOM #235 SHALL BE ACCESSIBLE. PROVIDE
 DETAIL FOR 11-4.16 WATER CLOSETS, (SEE
 FIGS. 28 & 29), 11-4.19 LAVS, (SEE FIGS.
 31 & 32), 11-4.21 SHOWERS, (SEE FIGS. 35
 36, & 37), AND 11-4.23 SHOWER ROOMS.
 ALSO SHOW ALL SUBSECTIONS FOR EACH SECT-
 ION. 11-4.3.1(11).
 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9.
 ROOM #210 SHALL BE ADAPTABLE. PROVIDE
 DETAIL SHOWING BACKING FOR GRAB BARS,
 CLEAR FLOOR SPACE, TURNING AREA, LAV
 HEIGHT, OPENING FOR WATER CLOSET, SHOWER
 CONTROLS, CURB, BACKING FOR SHOWER GRAB
 BARS ECT. 11-4.1.3(11).
 3) SHTS A2.1, A2.2, & A5.2 DETAIL #11.
 BREAK ROOM SINK SHALL COMPLY WITH SECT-
 ION 11-4.24 AND ALL SUBSECTIONS. PROVIDE
 A DETAIL.
 4) SHT P-1 WATER ISOMETRIC AT DRINKING
 FOUNTAIN. AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM DIAGRAM.
 5) SHT P-1 SUBMIT WATER & SANITARY ISO-
 METRICS FOR BREAK ROOM SINK. SECTION
 104.3.1.1. WATER HAMMER ARRESTOR REQUIR-
 ED FOR DISHWASHER. SECTION 604.9
 6) SHT P-1 PLUMBING NOTES: #12 AIR
 CHAMBERS ARE NOT APPROVED. DELETE REF-
 ERENCE.
 7) SHT P-2 FOLLOWING INFORMATION REQUIR-
 ED FOR APPLICATION FOR GAS PERMIT.
 SEPARATE PERMIT REQUIRED FOR GAS.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  