| 2003-12-31 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1, PLEASE CLARIFY 8 X 8 | | | DUCT IN THE WAITING ROOM 200, IS THIS | | | DUCT RUNNING THROUGH A EGRESS STAIRWAY? | | | | | | 2.PLAN SHEET M-2 EXISTING MECHANICAL | | | ROOM.DOES THIS SPACE HAVE ANY TYPE | | | OF EXISTING VENTILATION? | | | | | | 3.M-2 INDICATES DETAIL FOR A FIRE | | | DAMPER INSTALLATION FOR "WALL TYPE" | | | PLEASE PROVIDE DETAIL FOR THE FIRE | | | DAMPERS INSTALLED IN THE FLOOR. | | | | | | 4.PLAN SHEET M-2 INDICATES NEW | | | EMERGENCY GENERATOR, WILL THIS WORK BE | | | DONE AT THIS TIME OR FUTURE?PLEASE | | | PROVIDE ADDITIONAL INFORMATION.PLEASE | | | PROVIDE MANUFACTURER SUBMITTAL DATA OR | | | CUT SHEETS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|