Plan Review Notes
Plan Review Notes For Permit 03120833
Permit Number 03120833
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-31 00:00:00DENIED:
 1.PLAN SHEET M-1, PLEASE CLARIFY 8 X 8
 DUCT IN THE WAITING ROOM 200, IS THIS
 DUCT RUNNING THROUGH A EGRESS STAIRWAY?
  
 2.PLAN SHEET M-2 EXISTING MECHANICAL
 ROOM.DOES THIS SPACE HAVE ANY TYPE
 OF EXISTING VENTILATION?
  
 3.M-2 INDICATES DETAIL FOR A FIRE
 DAMPER INSTALLATION FOR "WALL TYPE"
 PLEASE PROVIDE DETAIL FOR THE FIRE
 DAMPERS INSTALLED IN THE FLOOR.
  
 4.PLAN SHEET M-2 INDICATES NEW
 EMERGENCY GENERATOR, WILL THIS WORK BE
 DONE AT THIS TIME OR FUTURE?PLEASE
 PROVIDE ADDITIONAL INFORMATION.PLEASE
 PROVIDE MANUFACTURER SUBMITTAL DATA OR
 CUT SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.