| Plan Review Notes For Permit 03120833 |
| Permit Number |
03120833 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) PLEASE PROVIDE MORE DETAILS FOR | | | NEW EMERGENCY GENERATOR PLANNED FOR | | | THE ROOF. | | | | | | 3) PLEASE PROVIDE MORE DETAILS ON | | | DELUGE FIRE SPRINKLER HEADS, ITEM # 18 | | | ON PAGE A.1. | | | | | | 4) THE DOUBLE DOORS FOR THE EXISTING | | | EGRESS STAIR VESTIBULE APPEARS TO | | | SWING IN THE WRONG DIRECTION. SHOULD | | | THEY NOT SWING IN THE DIRECTION OF | | | EXIT TRAVEL. | | | | | | 5) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FM 200 RELOCATION FROM EXISTING | | | LOCATION TO THE NEW LOCATION. | | | | | | 6) PLEASE EXPLAIN WHY STAIR NEAR | | | WAITING 200 IS NOT SEPARATED FROM ALL | | | PORTIONS OF THE BUILDING. | | | | | | 7) TACTILE SIGNAGE IS REQUIRED AT | | | STAIRWAYS. | | | | | | 8) ALL SHAFTWAYS THAT ARE LARGE ENOUGH | | | FOR PERSONS TO FALL INTO MUST BE | | | MARKED SHAFTWAY WITH 6" HIGH LETTERS. | | | | | | 9) DOOR FROM RECEPTION 241 MAY SWING | | | TOO FAR INTO CORRIDOR. | | | | | | 10) PLEASE PROVIDE PRODUCT APPROVALS | | | FOR DIAMOND WIRE GLASS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|