Plan Review Notes
Plan Review Notes For Permit 03120833
Permit Number 03120833
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-02 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON GENERATOR.
 PLEASE PROVIDE MEANS OF DISC PER 230.72
 230.76,230.79.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE MAIN. SHOWN FOR PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]