| Plan Review Notes For Permit 03120833 |
| Permit Number |
03120833 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE PROVIDE MORE INFORMATION | | | ON GENERATOR. | | | PLEASE PROVIDE MEANS OF DISC PER 230.72 | | | 230.76,230.79. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW SERVICE MAIN. SHOWN FOR PANELS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|