| 2004-01-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03120833 |
| | ADD: 314 CLEMATIS ST. |
| | CONT: RAPP CONSTRUCTION |
| | TEL: (561)248-6411 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST BUILDING REVIW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2.1 SHOWS A RECONFIGURATION |
| | OF THE FRONT ENTRY STAIR. THE 2ND FLOOR |
| | DEMO SHEET ALSO INDICATES A DOOR REMOVED |
| | FROM HALLWAY 228. THIS RECONFIGURATION |
| | WITH RECEPTION AREA ELIMINATES THE 1 HR |
| | RATING OF THE STAIRWELL. |
| | 1006.1.3.1 PENETRATIONS INTO AND |
| | THROUGH A STAIRWAY ENCLOSURE ASSEMBLY |
| | ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, DUCTWORK AND EQUIPMENT NECESSARY |
| | FOR THE INDEPENDENT STAIR PRESSURIZATION |
| | SPRINKLER PIPING, STANDPIPES AND ELECTRI |
| | CALCONDUIT SERVING THE STAIRWAY AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO |
| | TECTED IN ACCORDANCE WITH 705.4 |
| | 1006.1.4 THERE SHALL BE NO ENCLOSED |
| | USEABLE SPACE WITHIN AN EXIT ENCLOSUE, |
| | INCLUDING UNDER STAIRS. |
| | |
| | 2)1012.1.2 EGRESS DOORS SHALL BE SIDE |
| | SWINGING TYPE. DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS FOR THE FOLLOWING: |
| | DOUBLE DOORS LEADING TO THE REAR EXIT |
| | STAIRS. |
| | |
| | 3) SERVER ROOM 216: RAMP, |
| | 11-4.8.2 SLOPE & RISE. THE LEAST |
| | POSSIBLE SLOPE SHALL BE USED FOR ANY |
| | RAMP. THE MAXIMUM SLOPE FOR A RAMP IN |
| | NEW CONSTRUCTION SHALL BE 1 TO 12. THE |
| | MAXIMUM RISE FOR RUN SHALL BE 30" (SEE |
| | FIGURE 16). |
| | 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARENCE. |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS |
| | A RISE GREATER THAN 6" OR A HORIZONTAL |
| | PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 4) PRIVATE BATHROOM 210, INSWING DOOR: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 5) THE DOORSCHEDULE DOESN"T INDICATE |
| | THE RATED DOORS FOR EXIT ACCESS COORIDOR |
| | OR EXITS. TABLE 705.1.2 |
| | |
| | 6) THE 1/4" DIAMOND WIRE GLASS, PROVIDE |
| | RATING ON THE GLAZING AND FRAME.SEE |
| | TABLE 705.1.3.6/ SEC 705.1.3.6.2. |
| | SEE A-5.1 DETAIL "03", SIZE LIMITATION |
| | OF 54" VERTICAL TABLE 705.1.3.6. |
| | |
| | 7) SHEET A2.1 NOTE# 7 NEW WINDOWS AND |
| | DELUGE CURTAIN. |
| | 705.1.1.2 EVERY EXTERIOR WALL WITHIN |
| | 15 FT. OF THE PROPERTY LINE SHALL BE |
| | EQUIPPED WITH OPENING PROTECTIVES. THE |
| | DELUGE SYSTEM WILL REQUIRE GOING TO THE |
| | BOARD OF ADJUSTMENT & APPEAL FOR A VAR- |
| | IANCE UNDER ALTERNATE MEANS AND METHODS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |