2004-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST.
 CONT: RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIW
 ACTION: DENIED
  
 1) SHEET A-2.1 SHOWS A RECONFIGURATION
 OF THE FRONT ENTRY STAIR. THE 2ND FLOOR
 DEMO SHEET ALSO INDICATES A DOOR REMOVED
 FROM HALLWAY 228. THIS RECONFIGURATION
 WITH RECEPTION AREA ELIMINATES THE 1 HR
 RATING OF THE STAIRWELL.
 1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
 1006.1.4 THERE SHALL BE NO ENCLOSED
 USEABLE SPACE WITHIN AN EXIT ENCLOSUE,
 INCLUDING UNDER STAIRS.
  
 2)1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 DOUBLE DOORS LEADING TO THE REAR EXIT
 STAIRS.
  
 3) SERVER ROOM 216: RAMP,
 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 4) PRIVATE BATHROOM 210, INSWING DOOR:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5) THE DOORSCHEDULE DOESN"T INDICATE
 THE RATED DOORS FOR EXIT ACCESS COORIDOR
 OR EXITS. TABLE 705.1.2
  
 6) THE 1/4" DIAMOND WIRE GLASS, PROVIDE
 RATING ON THE GLAZING AND FRAME.SEE
 TABLE 705.1.3.6/ SEC 705.1.3.6.2.
 SEE A-5.1 DETAIL "03", SIZE LIMITATION
 OF 54" VERTICAL TABLE 705.1.3.6.
  
 7) SHEET A2.1 NOTE# 7 NEW WINDOWS AND
 DELUGE CURTAIN.
 705.1.1.2 EVERY EXTERIOR WALL WITHIN
 15 FT. OF THE PROPERTY LINE SHALL BE
 EQUIPPED WITH OPENING PROTECTIVES. THE
 DELUGE SYSTEM WILL REQUIRE GOING TO THE
 BOARD OF ADJUSTMENT & APPEAL FOR A VAR-
 IANCE UNDER ALTERNATE MEANS AND METHODS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026