| Plan Review Notes For Permit 03120818 |
| Permit Number |
03120818 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-31 00:00:00 | DENIED: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | 1.OUTSIDE AIR CALCULATIONS PER 2001 | | | FBC(M) TABLE 403.3. | | | | | | 2.PLAN SHEET M2 DETAIL 4, CONDENSATE | | | FROM THE RTU TO CONNECT TO THE FLOOR | | | DRAIN IN TENANTS SPACE.CONDENSATE | | | SHALL DISCHARGE INTO THE STORM DRAIN NOT | | | INTO THE SANITARY PER CITY CODE SEC. | | | 90-125(B)(5).PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|