| Plan Review Notes For Permit 03120818 |
| Permit Number |
03120818 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-29 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLANS MUST CONTAIN ORIGINAL | | | SIGNATURE BY THE ARCH AND ENGINEER OF | | | RECORD PER FS 481.221 AND FS 471.025 | | | PLEASE SEE THAT BOTHS SETS MUST CONTAIN | | | ORIG SIG FOR ALL TRADES WEATHER OR NOT | | | COMMENT IS MADE FROM OTHER REVIEWERS. | | | | | | 2)NOTE: PLEASE CLARIFY/SHOW RECEPTS | | | REQ'D FOR "SHOW" WINDOW. PER 210.62, AND | | | 220.12A | | | | | | 3)NOTE: PLEASE CLARIFY CIRCUITING FOR | | | EM/EXT LTS PER 700.12E | | | | | | 4)NOTE: PLEASE NOTE OR SHOW TRACK LIGHT- | | | ING LOADS PER 220.12B. | | | | | | NOTE: JUST AN FYI, THESTATE OF FL | | | ADOPTED THE 2002 NEC 7/1/2003. | | | PLANS NOTE 1993 OR LATEST ADOPTED. THIS | | | IS ONLY A NOTE FOR INFORMATION. | | | | | | 5)NOTE: PLEASE INCLUDE ALL LICENSE #`S | | | ON TITLE BLOCK AS SET FORTH PER FAC | | | 61G15-23.002. | | | REQ'D ALSO FOR ARCH'S PER 61G1-16.004 | | | OF THE FAC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|