2003-12-29 00:00:00************** UNSAT ***************
  
 1)NOTE: PLANS MUST CONTAIN ORIGINAL
 SIGNATURE BY THE ARCH AND ENGINEER OF
 RECORD PER FS 481.221 AND FS 471.025
 PLEASE SEE THAT BOTHS SETS MUST CONTAIN
 ORIG SIG FOR ALL TRADES WEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS.
  
 2)NOTE: PLEASE CLARIFY/SHOW RECEPTS
 REQ'D FOR "SHOW" WINDOW. PER 210.62, AND
 220.12A
  
 3)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM/EXT LTS PER 700.12E
  
 4)NOTE: PLEASE NOTE OR SHOW TRACK LIGHT-
 ING LOADS PER 220.12B.
  
 NOTE: JUST AN FYI, THESTATE OF FL
 ADOPTED THE 2002 NEC 7/1/2003.
 PLANS NOTE 1993 OR LATEST ADOPTED. THIS
 IS ONLY A NOTE FOR INFORMATION.
  
 5)NOTE: PLEASE INCLUDE ALL LICENSE #`S
 ON TITLE BLOCK AS SET FORTH PER FAC
 61G15-23.002.
 REQ'D ALSO FOR ARCH'S PER 61G1-16.004
 OF THE FAC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  