Plan Review Notes
Plan Review Notes For Permit 03120818
Permit Number 03120818
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120818
 ADD: 1801 PALM BEACH LAKES BLVD
 SUITE# 136
 CONT: THE FOSHEE CO INC
 TEL: (904)993-7297
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) 413.8 AUTOMATIC FIRE SPRINKLER
 SYSTEM, TO BE SUPPLIED WITH BUILDING
 PERMIT SET OF PLANS.
  
 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026