2004-07-12 00:00:00*********** UNSAT ****************
 ********** UNSAT 4TH TIME ***********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 STILL NOT MEET 220.31B.
 PLEASE SEE COMMENTS FROM PREVIOUS REVIEW
 -S.
 DERATING OF LOADS ON PANEL 'B' IS BEING
 TAKEN TWICE. THIS IS NOT PERMITTED.
  
  
 2)NOTE: PER LAST CONVERSATION WITH
 MR JAMES DEMARS, HIS LEGAL SIGNATURE
 WOULD BE USED UPON SIGNING AND SEALING
 OF PLANS. SIGNATURE ON PLANS DO NOT
 CORRELATE WITH PREVIOUS LETTERS.
 MR. DEMARS WAS TOLD HIS LEGAL SIGNATURE
 WAS REQUIRED PER FLORIDA STATUES. HE WAS
 ASKED TO SIGN AS PREVIOUS CORRESPONDENCE
 LETTER PERTAINING TO THE 4X FEE.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES THAT CONTAIN A TITLE BLOCK
 FOR ARCHITECT OF RECORD.
 FS 481.221.
  
 PLEASE SEE A 4X FEE WILL BE PENDING PER
 MEETING WITH NEIL MELICK BLDG OFFICAL.
 ONE COPY OF ELECTRICAL PLANS ARE BEING
 REATINED FOR RECORD AND SHALL BE PLACED
 INTO PREVIOUS FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 PLEASE CALL IN ORDER TO SET UP A MEETING
 IF SO DESIRED.
  