Plan Review Notes
Plan Review Notes For Permit 03120778
Permit Number 03120778
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-16 00:00:00************ UNSAT 3 TIME ***********
  
 PLEASE SEE NOTES FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 TO MEET 2002 NEC.ART 220
 PLEASE SEE ADDTIONAL LOADS BEING ADDED
 TO EXISTING DO NOT FALL UNDER THE SAME
 LOAD CALCULATIONS AS NEW.
 PLEASE SEE 220.31B. PLEASE SEE LOADS
 ON PLANS/PANELS DO NOT MEET 220.
  
 2)NOTE: PLEASE SEE NOTE #9, THIS STILL
 SHOWS SD'S TO BE WIRED AHEAD OF SWITCH-
 -ING ON BATH AND KIT LIGHTING CIRCUIT,
 AND BEDRMSD TO BE ARC FAULT.?
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE
 WIRED IN-LINE W/ EACH OTHER. IF SD'S IN
 BEDROOMS ARE REQUIRED TO BE ARC FAULT
 PROTECTED, THIS WOULD BE THAT ENTIRE
 BRANCH CIRCUIT. NOT JUST THAT SD.
  
 3)NOTE: PLEASE SEE NOTICE WAS GIVEN TO
 DESIGN PROFESSIONAL ON PREVIOUS REVIEW
 PERTAINING TO FS 553.80(2)(B).
 WHICH REQUIRES: " THE LOCAL GOVERMENT
 SHALL IMPOSE, EACH TIME AFTER THE THIRD
 SUCH REVIEW THE PLANS ARE REJECTED FOR
 THAT CODE VIOLATION A FEE OF FOUR TIMES
 THE AMOUNT OF THE PORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW".
 PLEASE SEE ATTACHED BZ 242709 $1,227.98
 THIS FEE MUST BE PAID BEFORE PLANS MAY
 BE RESUBMITTED FOR REVIEW.
 ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED FOR FILE.
  
 PLEASE SEE THESE NOTES MUST BE ADDRESSED
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]