| Date |
Text |
| 2004-05-19 00:00:00 | ********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE NOTES ON FIRST REVIEW |
| | PERTAINING TO ELECTRICAL LOAS CALCULAT- |
| | IONS PER NEC 220. |
| | PLEASE SUBMIT LOAD CALCS TO MEET 220 FOR |
| | RESIDENTIAL. |
| | |
| | 2)NOTE: PLEASE SEE NOTE# 9 MENTIONS |
| | SMOKE DETECTORS TO BE ON BATH/KIT CIR- |
| | -CUIT, PLEASE SEE 2002 NEC, ALL OUTLETS, |
| | RECETPS/LTS, FANS AND SMOKE DETECTORS |
| | MUST BE ON ARC FAULT CIRCUITS. |
| | SD WILL BE REQ'D IN THIS ADAPTABLE |
| | SLEEPING ROOM. |
| | |
| | 3)NOTE: PLEASE SUBMIT NOTORIZED LETTER |
| | FOR SIGNATURE. MUST CONTAIN ALL LEGAL |
| | INFORMATION THAT IS REQ'D OF NOTARY. |
| | MUST ALSO BE SIGNED AND SEALED PER ARCH. |
| | PLEASE ALSO REMOVE NOTE IN THE MIDDLE |
| | OF ELECTRICAL PLANS WHICH HAS NOTHING |
| | TO DO WITH ELECTRICAL CODE COMPLIANCE. |
| | ANY RESPONSE TO BLDG DEPT COMMENTS MAY |
| | BE DONE IN A PROFESSIONAL MANNER IN |
| | LETTER FORM. |
| | WE WILL BE RETAINING ONE COPY OF EACH |
| | ELECTRICAL SUBMITTED PLANS FOR RECORD. |
| | |
| | 4)NOTE: PLEASE SEE NOTE #6 FROM FIRST |
| | REVIEW. SHOWS ATTACHED TO GRND ROD AND |
| | COLD WATER BUT NOT TO REQ'D FOOTER STEEL |
| | PER 250.50 |
| | |
| | 5)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS. |
| | |
| | |
| | PLEASE REMOVE ALL/OLD VOIDED SHEEST AND |
| | ONLY INSERT NEW SHEETS FOR TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |