Plan Review Notes
Plan Review Notes For Permit 03120778
Permit Number 03120778
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-19 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES ON FIRST REVIEW
 PERTAINING TO ELECTRICAL LOAS CALCULAT-
 IONS PER NEC 220.
 PLEASE SUBMIT LOAD CALCS TO MEET 220 FOR
 RESIDENTIAL.
  
 2)NOTE: PLEASE SEE NOTE# 9 MENTIONS
 SMOKE DETECTORS TO BE ON BATH/KIT CIR-
 -CUIT, PLEASE SEE 2002 NEC, ALL OUTLETS,
 RECETPS/LTS, FANS AND SMOKE DETECTORS
 MUST BE ON ARC FAULT CIRCUITS.
 SD WILL BE REQ'D IN THIS ADAPTABLE
 SLEEPING ROOM.
  
 3)NOTE: PLEASE SUBMIT NOTORIZED LETTER
 FOR SIGNATURE. MUST CONTAIN ALL LEGAL
 INFORMATION THAT IS REQ'D OF NOTARY.
 MUST ALSO BE SIGNED AND SEALED PER ARCH.
 PLEASE ALSO REMOVE NOTE IN THE MIDDLE
 OF ELECTRICAL PLANS WHICH HAS NOTHING
 TO DO WITH ELECTRICAL CODE COMPLIANCE.
 ANY RESPONSE TO BLDG DEPT COMMENTS MAY
 BE DONE IN A PROFESSIONAL MANNER IN
 LETTER FORM.
 WE WILL BE RETAINING ONE COPY OF EACH
 ELECTRICAL SUBMITTED PLANS FOR RECORD.
  
 4)NOTE: PLEASE SEE NOTE #6 FROM FIRST
 REVIEW. SHOWS ATTACHED TO GRND ROD AND
 COLD WATER BUT NOT TO REQ'D FOOTER STEEL
 PER 250.50
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
  
 PLEASE REMOVE ALL/OLD VOIDED SHEEST AND
 ONLY INSERT NEW SHEETS FOR TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]