| Date |
Text |
| 2004-05-04 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER PER 220. LOADS FROM PANEL "B" CAN |
| | NOT BE DERATED TWICE. |
| | PLEASE ALSO SEE LOADS FOR A/C'S PER |
| | 220. |
| | |
| | 3)NOTE: PLEASE SEE 424.3B FOR OCP OF |
| | 8KW HEAT. |
| | |
| | 4)NOTE: SD REQ'D IN CABANA RM. THIS IS |
| | AN ADAPTABLE SLEEPING RM PER NFPA-72 |
| | |
| | 5)NOTE: PLEASE ALSO PROVIDE ARC FAULT |
| | PROTECTION PER 210.12. 2002 NEC. |
| | |
| | 6)NOTE: PLEASE SHOW GROUNDING FOR PANEL |
| | 'B' TO BOND TO NEW FOOTER STEEL AND ANY |
| | METALLIC WATER PIPE. |
| | 250.50/250.32 |
| | |
| | 7)NOTE: PLEASE PROVIDE COPY OF DRVIERS |
| | LICENSE FOR VERIFICATION OF LEGAL |
| | SIGNATURE. WE HAVE NOW STARTED A FILE |
| | FOR ARCH'S AND ENGINEER'S SIGNATURES. |
| | THIS MUST BE HOW LICENSE WAS SIGNED WITH |
| | THE STATE. ANY PERSONEL INFORMATION LIKE |
| | ADDRESS AND LICENSE # MAY BE CROSSED OUT |
| | FS 481.221 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |