Plan Review Notes
Plan Review Notes For Permit 03120778
Permit Number 03120778
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-04 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220. LOADS FROM PANEL "B" CAN
 NOT BE DERATED TWICE.
 PLEASE ALSO SEE LOADS FOR A/C'S PER
 220.
  
 3)NOTE: PLEASE SEE 424.3B FOR OCP OF
 8KW HEAT.
  
 4)NOTE: SD REQ'D IN CABANA RM. THIS IS
 AN ADAPTABLE SLEEPING RM PER NFPA-72
  
 5)NOTE: PLEASE ALSO PROVIDE ARC FAULT
 PROTECTION PER 210.12. 2002 NEC.
  
 6)NOTE: PLEASE SHOW GROUNDING FOR PANEL
 'B' TO BOND TO NEW FOOTER STEEL AND ANY
 METALLIC WATER PIPE.
 250.50/250.32
  
 7)NOTE: PLEASE PROVIDE COPY OF DRVIERS
 LICENSE FOR VERIFICATION OF LEGAL
 SIGNATURE. WE HAVE NOW STARTED A FILE
 FOR ARCH'S AND ENGINEER'S SIGNATURES.
 THIS MUST BE HOW LICENSE WAS SIGNED WITH
 THE STATE. ANY PERSONEL INFORMATION LIKE
 ADDRESS AND LICENSE # MAY BE CROSSED OUT
 FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]