| Plan Review Notes For Permit 03120737 |
| Permit Number |
03120737 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-20 00:00:00 | | | | BUILDING PROVISO: | | | 1)704.2.1.4 CORRIDOR PARTITIONS, | | | SMOKESTOP PARTITIONS, HORIZONTAL EXIT | | | PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO | | | THEAUTHORITY HAVING JURISDICTION. SUCH | | | IDENTIFICATION SHALL BE ABOVE ANY | | | DECORATIVECEILING CEILING AND IN | | | CONCEALED SPACES.SUGGESTED WORDING" | | | FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | GLAZING WITHIN 24" OF THE LATCH SIDE OF | | | A DOORWAY TEMPERED GLAZING REQUIRED. |
|