Plan Review Notes
Plan Review Notes For Permit 03120737
Permit Number 03120737
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASESHOW ALL CIRCUITING ON
 PLANS AND PLEASE CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE CLARIFY LOCATION OF PANEL
 , SHOWN IN WHAT APPEARS TO BE A CLOSET/
 STORAGE SPACE/AREA. PLEASE SEE 408.7 AND
 110.26.
  
 3)NOTE: PLEASE CLARIFY TO WHAT EXTENT
 OF SERVICE IS TO REWIRED. SERVICE NOTE
 MENTIONS REWIRE BUT NO OTHER INFORMATION
 WAS GIVEN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]