| Plan Review Notes For Permit 03120697 |
| Permit Number |
03120697 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-04-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} ANY REVISIONS MADE TO AN ENGINEERED | | | SET OF WRAWINGS MUST BE MADE BY THE | | | DESIGNER OF RECORD. F.S.471. | | | | | | 2} CU #2 NEEDS A DISCONNECT. | | | | | | 3} 210.63 RECEP @CU EQUIP. | | | | | | 4} COMPLY WITH 210.52(E). | | | | | | 5} COMPLY WITH 905.2.2 FBC RE: SD'S @ | | | STAIRWELLS. | | | | | | 6} 210.52(D) SECOND FLOOR BATH. | | | | | | 7} 905.2.2 2ND FLOOR STAIRS. | | | | | | PLEASE SEE APPROVED PLANS AND CORRELATE | | | WITH REVISIONS BEFORE RESUBMITTING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|