| Plan Review Notes For Permit 03120697 |
| Permit Number |
03120697 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT P-3 SANT. RISER DIAGRAM, MASTER | | | BATH SHOWER SHALL BE MINIMUM OF 2" PIPE | | | TABLE 709.1 | | | 2) SHT P-3 SANT. RISER DIAGRAM, WASH | | | MACHINE REQUIRES A STANDPIPE, AND THE | | | CLEANOUT SHALL BE LOCATED MINIMUM OF 4 | | | FEET ABOVE FLOOR. 406.3 - 708.10 | | | 3) SHT P-3 WATER RISER DIAGRAM, AIR | | | CHAMBERS ARE NOT APPROVED. 604.9 PLEASE | | | DELETE FROM RISER. | | | 4) SHT P-3 WATER HEATER DETAIL, WATER | | | HEATERS INSTALLED ABOVE THE GROUND FLOOR | | | SHALL BE INSTALLED IN A PAN. 804.5 | | | 5) SHT P-3 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL REQUIRED IF THERE IS A | | | RPZ BACKFLOW ON THE WATER SERVICE TO THE | | | RESIDENCE. 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|