2004-02-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-3 SANT. RISER DIAGRAM, MASTER
 BATH SHOWER SHALL BE MINIMUM OF 2" PIPE
 TABLE 709.1
 2) SHT P-3 SANT. RISER DIAGRAM, WASH
 MACHINE REQUIRES A STANDPIPE, AND THE
 CLEANOUT SHALL BE LOCATED MINIMUM OF 4
 FEET ABOVE FLOOR. 406.3 - 708.10
 3) SHT P-3 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. 604.9 PLEASE
 DELETE FROM RISER.
 4) SHT P-3 WATER HEATER DETAIL, WATER
 HEATERS INSTALLED ABOVE THE GROUND FLOOR
 SHALL BE INSTALLED IN A PAN. 804.5
 5) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED IF THERE IS A
 RPZ BACKFLOW ON THE WATER SERVICE TO THE
 RESIDENCE. 607.3.2
  