Plan Review Notes
Plan Review Notes For Permit 03120697
Permit Number 03120697
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM SHOWS #3/0 FEEDERS
 TO PANEL "A",THE PANEL SCHEDULE
 INDICATES #2/0,PLEASE CORRELATE.
  
 2} PLEASE CHECK ELECTRICAL NOTES. #16
 SPECS.#12 WIRE,BUT PANEL SCHEDULE SHOWS
 #14. #37 SHOULD REFER TO 250.66 FOR GEC
 ART.
  
 3} THE OVERHEAD RISER WOULD APPEAR TO BE
 IN VIOLATION OF 230.9(A) AND/OR (B).SEE
 SHEET A-4 ELEVATION. INDICATE
 COMPLIANCE.
  
 4} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 5} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12' RULE.SEVERAL LOCATIONS
 DO NOT COMPLY, SEE REVIEWED SET.
  
 6} THE CONDENSER DISCONNECTS DO NOT
 APPEAR TO COMPLY WITH 110.26.
  
 7} SMOKE DETECTORS AT THE STAIRWELLS TO
 COMPLY WITH 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  