| 2004-02-09 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER DIAGRAM SHOWS #3/0 FEEDERS | | | TO PANEL "A",THE PANEL SCHEDULE | | | INDICATES #2/0,PLEASE CORRELATE. | | | | | | 2} PLEASE CHECK ELECTRICAL NOTES. #16 | | | SPECS.#12 WIRE,BUT PANEL SCHEDULE SHOWS | | | #14. #37 SHOULD REFER TO 250.66 FOR GEC | | | ART. | | | | | | 3} THE OVERHEAD RISER WOULD APPEAR TO BE | | | IN VIOLATION OF 230.9(A) AND/OR (B).SEE | | | SHEET A-4 ELEVATION. INDICATE | | | COMPLIANCE. | | | | | | 4} PLEASE SEE RECEPTS SERVING | | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | | SEC'S 1,2,3,4 AND 5 | | | | | | 5} PLEASE SHOW OUTLET SPACING PER | | | 210.52. 2',6',12' RULE.SEVERAL LOCATIONS | | | DO NOT COMPLY, SEE REVIEWED SET. | | | | | | 6} THE CONDENSER DISCONNECTS DO NOT | | | APPEAR TO COMPLY WITH 110.26. | | | | | | 7} SMOKE DETECTORS AT THE STAIRWELLS TO | | | COMPLY WITH 905.2.2 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|