Plan Review Notes
Plan Review Notes For Permit 03120633
Permit Number 03120633
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-17 00:00:00*************DENIED*********************
 1) PLEASE PROVIDE CUT SHEETS ON THE
 DEVICES TO BE INSTALLED.
  
 2) THERES NO HORN/STROBE DEVICES SHOWED
 ON THE PLAN TO NOTIFY THE OCCUPANTS
  
 3) ONLY APPROVED CENTRAL STATION BY WEST
 PALM BEACH FIRE RESCUE CAN DO MONITORING
 IN THE CITY.
  
 4) PLEASE REFERENCE NFPA 72 CHAPTER
 2-4.7 , 2-4.7.1 AND 2-4.7.2 ON
 COMBINATION SYSTEM (FIRE/BURGLAR).
  
 5) FIRE ALARM SYSTEM IS TO BE CLASS "A"
 OR FULLY ADDRESSABLE AND UL CERTIFICATE
 OF COMPLIANCE. ( PLEASE SEE ATTACHED )
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910