Plan Review Notes
Plan Review Notes For Permit 03120628
Permit Number 03120628
Review Stop P
Sequence Number 3
Notes
Date Text
2004-09-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT AP/P14.01 NO CHANGES NOTED ON THE
 WATER RISER DIAGRAMS IN UNITS B1 & C1.
 PLEASE CLARIFY. SECTION 104.2.1
 2) SHT AP/P14.02 CLEANOUT ARE REQUIRED
 MAXIMUM 100' IN BUILDING DRAIN. THESE
 HAVE BEEN DELETED ON THE LAYOUT, BUT ARE
 STILL ON THE BLDG. DRAIN ISOMETRIC. THE
 CLEANOUTS ON THE STACKS CAN NOT BE USED
 AS BLDG. DRAIN CLEANOUTS AS THEY ARE IN
 THE APARTMENTS AND ARE NOT ACCESSIBLE.
 SECTION 708.3.1
 3) SHT AP/P14.02 SANITARY PIPING MISSING
 TO BATHROOM IN UNIT C1. - FITTINGS DIS-
 CHARGING INTO THE BLDG. DRAIN ARE CONN-
 ECTING IN THE WRONG DIRECTION AGAINST
 THE FLOW. SECTIONS 706.3 & 104.2.1
 4) SHT AP/P14.04 NO CHANGES NOTED ON THE
 SAFETY PAN PIPING DIAGRAM. PLEASE CLARI-
 FY. SECTION 104.2.1
 5) SHT CH/P14.02 DOMESTIC WATER RISER,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 IN AN "EFFECTIVE RANGE" NEAR THE FIXTUR-
 ES, NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS
 SEE PROVISO ON STAMPED SET OF PLANS.
 SECTION 104.2.1
 6) SHT CH/P14.03 THERMAL EXPANSION CONT-
 ROL REQUIRED. THIS HAS BEEN DELETED AND
 IS REQUIRED PER SECTION 607.3.2
 7) REVISIONS ARE REQUIRED TO BE SUBMITT-
 ED UNDER EACH PERMIT NUMBER FOR EACH OF
 THE BUILDINGS. WHEN RESUBMITTING REVIS-
 IONS, CLUBHOUSE REVISIONS ONLY SHALL BE
 SUBMITTED UNDER THE CLUBHOUSE PERMIT
 NUMBER. THEN EACH BUILDING REVISION
 SHALL BE SUBMITTED SEPARATELY. SECTION
 1094.2.1.3.
  