| 2004-08-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) REVISIONS HAVE BEEN SUBMITTED UNDER |
| | THE PERMIT NUMBER FOR THE CLUBHOUSE. NO |
| | REVISIONS FOR THE CLUBHOUSE WERE SUBMIT- |
| | TED. PLEASE RESUBMIT UNDER PERMIT NUMBER |
| | FOR EACH BUILDING. SINCE THIS IS A MAST- |
| | ERED PROJECT. A SET OF REVISIONS SHALL |
| | BE REQUIRED FOR EACH BUILDING. |
| | 2) PREVIOUS REVISIONS FOR THIS PROJECT |
| | ARE NUMBERS 1 & 2. NO REVISION NUMBER IS |
| | SHOWN FOR THIS CHANGE. RESUBMIT SHEETS |
| | WITH NEXT REVISION NUMBER IN SEQUENCE. |
| | SECTION 104.2.1 |
| | 3) ALL REVISIONS TO A SIGNED & SEALED |
| | SET OF PLANS SHALL BE SIGNED/SEALED/DAT- |
| | ED BY THE ENGINEER OF RECORD. FAC 61G15- |
| | 23.002(1)(2) & FS 471.025 |
| | 4) SHT AP P14.02 CLEANOUTS REQUIRED BY |
| | SECTION 708.3.2 WERE REMOVED ON THIS RE- |
| | VISION. MAXIMUM 100' BETWEEN CLEANOUTS. |
| | 5) SHT AP P14.03 SHEET SUBMITTED BY GULF |
| | COAST PLUMBING INDICATES IN NOTE #3 THAT |
| | STACKS FOR BATHROOM & LAUNDRY STACKS FOR |
| | UNITS "B1 & "C1" WERE CHANGED, BUT THE |
| | BATHROOM STACKS HAVE NOT CHANGED. PLEASE |
| | CLARIFY. SECTION 104.2.1 |
| | 6) SHT AP P14.04 RISER 3SA HAS BEEN DE- |
| | LETED, AND HAS BEEN DELETED ON THE BLDG. |
| | DRAIN RISER SHT AP P14.02. PLEASE CLARI- |
| | FY. |
| | |