Plan Review Notes
Plan Review Notes For Permit 03120628
Permit Number 03120628
Review Stop P
Sequence Number 2
Notes
Date Text
2004-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) REVISIONS HAVE BEEN SUBMITTED UNDER
 THE PERMIT NUMBER FOR THE CLUBHOUSE. NO
 REVISIONS FOR THE CLUBHOUSE WERE SUBMIT-
 TED. PLEASE RESUBMIT UNDER PERMIT NUMBER
 FOR EACH BUILDING. SINCE THIS IS A MAST-
 ERED PROJECT. A SET OF REVISIONS SHALL
 BE REQUIRED FOR EACH BUILDING.
 2) PREVIOUS REVISIONS FOR THIS PROJECT
 ARE NUMBERS 1 & 2. NO REVISION NUMBER IS
 SHOWN FOR THIS CHANGE. RESUBMIT SHEETS
 WITH NEXT REVISION NUMBER IN SEQUENCE.
 SECTION 104.2.1
 3) ALL REVISIONS TO A SIGNED & SEALED
 SET OF PLANS SHALL BE SIGNED/SEALED/DAT-
 ED BY THE ENGINEER OF RECORD. FAC 61G15-
 23.002(1)(2) & FS 471.025
 4) SHT AP P14.02 CLEANOUTS REQUIRED BY
 SECTION 708.3.2 WERE REMOVED ON THIS RE-
 VISION. MAXIMUM 100' BETWEEN CLEANOUTS.
 5) SHT AP P14.03 SHEET SUBMITTED BY GULF
 COAST PLUMBING INDICATES IN NOTE #3 THAT
 STACKS FOR BATHROOM & LAUNDRY STACKS FOR
 UNITS "B1 & "C1" WERE CHANGED, BUT THE
 BATHROOM STACKS HAVE NOT CHANGED. PLEASE
 CLARIFY. SECTION 104.2.1
 6) SHT AP P14.04 RISER 3SA HAS BEEN DE-
 LETED, AND HAS BEEN DELETED ON THE BLDG.
 DRAIN RISER SHT AP P14.02. PLEASE CLARI-
 FY.
  