| Plan Review Notes For Permit 03120628 |
| Permit Number |
03120628 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-05 00:00:00 | PASSED/PROVISO | | | REVISION REQUIRED FOR SHEET CH/P14.02 | | | | | | 1) SHT CH/P14.02 WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | | SHOWN. PDI-WH 201 AND MANUF. INSTALLAT- | | | ION INSTRUCTIONS. - SIZE WATER HAMMER | | | ARRESTOR FOR ALL 5 WASH MACHINES. | | | | | | 2) INDICATE ON PLANS THAT AN RPZ BACK- | | | FLOW IS REQUIRED ON THE WATER SERVICE TO | | | THE CLUBHOUSE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|