2005-07-08 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. THREE SETS OF PLANS REQUIRED. ONLY
 TWO SETS OF REVISIONS WERE SUBMITTED.
 SECTION 105.3.
 2. SHT P14.05 THERMAL EXPANSION CONTROL
 IS REQUIRED PER SECTION 607.3.2. THE
 THERMAL EXPANSION VALVE HAS BEEN DELETED
 ON THE WATER HEATER PIPING DETAIL.
 PLEASE CLARIFY HOW THIS WILL BE
 ADDRESSED.
  