| Plan Review Notes For Permit 03120609 |
| Permit Number |
03120609 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT N-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | | REFLECT THE FLOOR PLAN: | | | A) WASH MACHINE REQUIRES A TRAP AND A | | | CLEANOUT. 1002.1 & 708.10 | | | B) TUB NOT VENTED AND W/C SHALL CONNECT | | | DOWNSTREAM OF THE LAV. 901.2.1 AND | | | 104.2.1.1. | | | 2) SEE RED LINE CORRECTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|