2004-01-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT N-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN:
 A) WASH MACHINE REQUIRES A TRAP AND A
 CLEANOUT. 1002.1 & 708.10
 B) TUB NOT VENTED AND W/C SHALL CONNECT
 DOWNSTREAM OF THE LAV. 901.2.1 AND
 104.2.1.1.
 2) SEE RED LINE CORRECTIONS.
  