| Plan Review Notes For Permit 03120591 |
| Permit Number |
03120591 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-03-04 00:00:00 | PROVISO: | | | 1.A MINIMUM OF 4" AROUND THE AHU IS | | | REQUIRED PER 2001 FBC(M)603.1.3. | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | 3.DRYER EXHAUST SHALL TERMINATE | | | OUTSIDE THE BUILDING AND BE NON-SCREENED | | | WITH A BACKDRAFT DAMPER PER 2001 | | | FBC(M)504.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|