| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | ********** PROVISO *********** | | | | | | 1)NOTE: PLEASE SEE ELEVATRO MACHINE ROOM | | | AND PIT REQUIRES EACH A SEPARATE BRANCH | | | CIRCUIT FOR LIGHTING AND RECEPTS. | | | PLEASE ALSO SEE MISSING GFI RECEPT TO BE | | | LOCATED ON ELEVATOR MACHINE RM. | | | 620.23,620.24 | | | | | | 2)NOTE: PLEASE SEE EM LTS AND EXT LTS | | | REFERENCE TO A NOTE #2 TYP. | | | PLEASE SEE NOTE #2 ON "FIRST AND SECOND | | | FLR NOTES"REFERS TO ALL EM/EXT LTS TO | | | BE WIRED AHEAD OF APT UNIT LIGHTING | | | SWITCHES. | | | PLEASE SEE 210.25, COMMON AREA BRANCH | | | CIRCUITS MAY NOT BE CIRCUITED TO | | | DWELLING/APT UNITS. | | | PLEASE SEE PLANS FOR COMMON AREA APPEAR | | | TO BE CIRCUITED CORRECTLY TO A HOUSE | | | PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION. | | | NOTE #1 TO BE REVISED ON PLANS,CAN BE 8 | | | 1/2 X 11'S FOR REVISED PANEL SCHEDULE | | | AND ELEV RM LAYOUTS. | | | NOTE #2 CAN BE REVISED IN LTR FORM. | | | | | | PLEASE SUBMIT BEFORE FINAL/CO. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|