Plan Review Notes
Plan Review Notes For Permit 03120591
Permit Number 03120591
Review Stop E
Sequence Number 6
Notes
Date Text
2005-08-11 00:00:00********** PROVISO ***********
  
 1)NOTE: PLEASE SEE ELEVATRO MACHINE ROOM
 AND PIT REQUIRES EACH A SEPARATE BRANCH
 CIRCUIT FOR LIGHTING AND RECEPTS.
 PLEASE ALSO SEE MISSING GFI RECEPT TO BE
 LOCATED ON ELEVATOR MACHINE RM.
 620.23,620.24
  
 2)NOTE: PLEASE SEE EM LTS AND EXT LTS
 REFERENCE TO A NOTE #2 TYP.
 PLEASE SEE NOTE #2 ON "FIRST AND SECOND
 FLR NOTES"REFERS TO ALL EM/EXT LTS TO
 BE WIRED AHEAD OF APT UNIT LIGHTING
 SWITCHES.
 PLEASE SEE 210.25, COMMON AREA BRANCH
 CIRCUITS MAY NOT BE CIRCUITED TO
 DWELLING/APT UNITS.
 PLEASE SEE PLANS FOR COMMON AREA APPEAR
 TO BE CIRCUITED CORRECTLY TO A HOUSE
 PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 NOTE #1 TO BE REVISED ON PLANS,CAN BE 8
 1/2 X 11'S FOR REVISED PANEL SCHEDULE
 AND ELEV RM LAYOUTS.
 NOTE #2 CAN BE REVISED IN LTR FORM.
  
 PLEASE SUBMIT BEFORE FINAL/CO.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]