| 2005-02-03 00:00:00 | DENIED: | | | 1.PLAN SHEET M2.1 SECOND AND THIRD | | | FLOOR, AHU2-3 & 3-3,THE OUTSIDE AIR | | | APPEARS TO TERMINATE IN THE KITCHEN. | | | OUTSIDE AIR IS TO BE DUCTED TO A CLOSE | | | PROXIMITY OR INTO THE RETURN AIR SO THE | | | OUTSIDE AIR WILL BE CIRCULATED THROUGH | | | THE AHU. | | | | | | 2.RETURN AIR TO RTU-1 IS NOT SIZED | | | PROPERLY.PER 2001 FBC(M)601.4, | | | BALANCED RETURN REQUIRED. | | | | | | 3.RETURN AIR GRILLE TO RTU-1 IS | | | TERMINATING AT A RATED WALL BUT A FIRE | | | DAMPER IS NOT INDICATED. | | | | | | 4.PLANS DO NOT INDICATE THE VENTING | | | OR TERMINATION OF THE DRYER EXHAUST. | | | PLEASE CLARIFY. | | | | | | PLEASE NOTE, LOUVERED DOOR IS PART OF | | | THE RETURN AIR PLENUM AND SHALL BE NON | | | COMBUSTIBLE PER 2001 FBC(M)602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|