| 2004-06-07 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: IN RESPONSE TO PREVIOUS NOTES, |
| | A CERTIFICATE OF AUTHORIZATION # WAS ADD |
| | -ED TO SHEETS. THE FIRM NAME CORRESPOND- |
| | ING TO THAT CA# HAS NOW CHANGED. |
| | PLEASE SEE SOME SHEETS STILL CONTAIN |
| | OTHER FIRM NAME AND PLEASE SEE TITLE |
| | BLOCK ALSO CONTAINS OLD FIRM NAME EVEN |
| | ON REVISED SHEETS. |
| | OLD SHEETS WERE NOT CORRECTED. |
| | PLEASE SEE FS 471.023/ FAC 61G15-23.002 |
| | THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| | OR NOT COMMENT IS MADE FROM OTHER REVIEW |
| | -ERS. |
| | |
| | |
| | |
| | 2)NOTE: PLEASE SEE NEW ELECTRICAL SHEETS |
| | ARE NOW SEALED BY A NEW ENGINEER AND OLD |
| | SHEETS CONTAIN A DIFFERENT ENGINEER? |
| | PLEASE SEE FS 471.025 WHICH REQUIRES A |
| | "SIGNATURE". THIS SIGNATURE MUST BE AS |
| | SHOWN ON SEAL. NEW ENGINEERFIRST NAME |
| | ONLY CONTAINS AN INITIAL. PLEASE SIGN |
| | W/ LEGAL SIGNATURE. |
| | |
| | 3)NOTE: NOTE: ARC FAULT PROTECTION WILL |
| | BE REQ'D FOR SD'S IN SLEEPING AREAS |
| | PER 210.12 EVEN IF ON KITCHEN LT CIRCUIT |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLYINSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS MAY BE SUBMITTED |
| | FOR REFERENCE. SOME REVIEWS MAY REQUIRE |
| | THIS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |