| Plan Review Notes For Permit 03120591 |
| Permit Number |
03120591 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | A) COMMENT #4 FROM PREVIOUS REVIEW NOT | | | COMPLETLY ANSWERED. SHT P5.2 REMOVAL OF | | | HUB DRAIN AND CONDENSATE LINE DRAINING | | | IN TO IT IS NOT DELETED AS SUGGESTED. | | | B) COMMENT #5 FROM PREVIOUS REVIEW: | | | WORK SHEET FROM RODNEY COMPO REQUIRED AT | | | TIME OF PERMIT ISSUANCE. PLEASE SUBMIT. | | | C) COMMENT #6 FROM PREVIOUS REVIEW RE- | | | SPONSE NOTED, BUT AIR CHAMBERS ARE STILL | | | SHOWN ON WATER RISER DIAGRAMS. ALSO THE | | | WATER HAMMER ARRESTORS SHALL BE SHOWN ON | | | THE RISER DIAGRAM AT THE W/M, D.W. & THE | | | ICE MAKER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|