Plan Review Notes
Plan Review Notes For Permit 03120591
Permit Number 03120591
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) COMMENT #4 FROM PREVIOUS REVIEW NOT
 COMPLETLY ANSWERED. SHT P5.2 REMOVAL OF
 HUB DRAIN AND CONDENSATE LINE DRAINING
 IN TO IT IS NOT DELETED AS SUGGESTED.
 B) COMMENT #5 FROM PREVIOUS REVIEW:
 WORK SHEET FROM RODNEY COMPO REQUIRED AT
 TIME OF PERMIT ISSUANCE. PLEASE SUBMIT.
 C) COMMENT #6 FROM PREVIOUS REVIEW RE-
 SPONSE NOTED, BUT AIR CHAMBERS ARE STILL
 SHOWN ON WATER RISER DIAGRAMS. ALSO THE
 WATER HAMMER ARRESTORS SHALL BE SHOWN ON
 THE RISER DIAGRAM AT THE W/M, D.W. & THE
 ICE MAKER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]