| Plan Review Notes For Permit 03120591 |
| Permit Number |
03120591 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-04 00:00:00 | DENIED: | | | 1.REFERENCE RESPONSE LETTER, | | | MECHANICAL; COMMENT/RESPONSE #2 - | | | OUTSIDE AIR PROVIDED THROUGH HALLWAY. | | | PER 2001 FBC(M) 403.2.1 #1 VENTILATION | | | AIR SHALL NOT BE RECIRCULATED FROM ONE | | | DWELLING TO ANOTHER OR DISSIMILAR | | | OCCUPANCIES. | | | | | | 2.REFERENCE RESPONSE LETTER, | | | MECHANICAL - RESPONSE TO COMMENT #5, | | | VERTICAL RUNS MOVERD TO A FIRE RATED | | | SHAFT WEST OF THE ELEVATOR.PLANS DO | | | NOT INCLUDE A DETAIL OR UL # FOR THE | | | SHAFT ASSEMBLY.PLEASE PROVIDE DETIALS | | | FOR THE CONSTURCTION OF THE SHAFT. | | | | | | 3.COMMENT/RESPONSE #7, REFRIGERANT | | | LINES MOVED INTO SHAFT.PLEASE NOTE | | | SHAFT ENCLOSURE SHALL BE FIRE-RESISTANT | | | AND VENTED TO THE OUTSIDE OR TO THE | | | SPACE SERVED BY THE SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|