Plan Review Notes
Plan Review Notes For Permit 03120591
Permit Number 03120591
Review Stop E
Sequence Number 2
Notes
Date Text
2004-03-03 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE PLUMB COMMENTS ON FIRST
 REVIEW. TITLE BLOCKS ARE REQ'D TO HAVE
 ALL LICENSE #'S AS REQ'D UNDER
 FS 471.023 BE LISTED. THIS IS REQ'D FOR
 ALL SHEETS AND ALL TRADES. COMMENT WAS
 NOT MADE BY ELECTRICAL REVIEW DUE TO
 PLUMB MAKING COMMENT.
 PLEASE NOTE: COMMENT IS NOW BEING MADE
 BY ELECTRICAL AND NOT PLUMB HOWEVER
 THIS IS REQ'D PER FAC 61G15-23.002 FOR
 ALL.
  
 2)NOTE: PLEASE SEE PLANS NOW SHOW CIR-
 -CUITING AS REQUESTED ON FIRST REVIEW.
 PLEASE SEE 210.11C1, PLANS SHOW ONLY
 ONE SMALL APPLIANCE CIRCUIT.
  
 3)NOTE: PLEASE SEE 220.16A FOR MIN LOAD
 TO BE IN LOAD CALCULATIONS.
 SHOWN AS 1 KVA?
  
 4)NOTE: PLEASE CORRELATE CIRCUITS ON
 PLANS WITH PANEL SCHEDULE. PLEASE SEE
 SD'S AND STILL SHOWN ON WITH KITCHEN
 LTS? CIRCUIT # SEEMS TO AHVE BEEN
 CHANGED ON PLAN, BUT NOT PANEL SCHEDULES
  
 5)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS HAVE NOW BEEN ADDED, HOWEVER
 PLEASE SEE 250.24. EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC. AS SHOWN PARALLELS
 THE NEUTRAL. 250.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]