2004-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS ST
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)756-0540
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS THE RESULTS OF A
 MEETING WITH SHERRY PILAND/ NEIL MELICK
 AS TO WHAT PARTS OF THE BUILDING WILL
 FALL UNDER THE HISTORIC PERVIEW AND
 WHAT
 PARTS WILL FALL UNDER BUILDING FOR
 REVIEW.
  
 1) COMMENT# 4 FROM PREVIOUS REVIEW:
 903.8.1 BUILDINGS 3 STORIES OR MORE.
 ANY
 BUILDING 3 STORIES SHAL BE EQUIPPED
 WITH
 AN APPROVED AUTOMATIC FIRE SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH
 903.1
 RESPONCE: EXISTING SYSTEM, GC TO SUBMIT
 FIRE SPRINKLER DRAWINGS AS PART OF THIS
 SUBMITTAL.
 NO FIRE SPRINKLER PLANS WERE SUBMITTED!
  
 2) COMMENT# 14 FROM PREVIOUS REVIEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: STOREFRONT SYSTEM
 RESPONCE: GC SHALL SUBMIT THE TEST
 REPORTS REQUIRED FOR THESES ITEMS.
 NO PRODUCT TESTING REPORTS SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) COMMENT #20 FROM PREVIOUS REVIEW
 DEALS WITH REINFORCED AREAS FOR
 ADAPTABLE BATHROOMS THERE IS NO
 INFORMA-
 TION FOR BACKING FOR THE SHOWER, TAKEN
 FROM FLORIDA ACCESSIBILITY CODE AND THE
 FAIR HOUSING CODE.
  
 4) COMMENT #21 FROM PREVIOUS REVIEW:
 DEALS WITH THE FIRST FLOOR ENTRY DOORS.
 SHEET A-0 INDICATES THAT THERE IS A
 2'-6" SET BACK, SHEET A2.1 INDICAES A
 PAIR OF 3'-0" OVERHANGING INTO THE
 RIGHT OF WAY 6".
  
 5) GUIDELINES FOR REHABILITING HISTORIC
 BUILDINGS, FLORIDA BUILDING CODE,APPX.
 D
 THE SAME MEETING BETWEEN NEIL MELICK,
 SHERRY PILAND AND MYSELF, IT WAS
 DISCUSS
 ED THAT THE WINDOWS WOULD NOT BE
 REPLACED, HISTORIC RECOMMENDATIONS. THE
 TOPIC OF ENERGY RETROFITTING WAS
 DISCUSS
 ED. SINCE THE WINDOWS WERE NOT TO BE
 RE-
 PLACED IT WAS DETERMINED TO HELP MAKE
 THE BUILDING MORE ENERGY EFFICIENT AND
 WORK ING WITH THE EXISTING WINDOWS, TO
 IMPROVE THERMAL EFFICIENCY WITH
 WEATHER-
 STRIPPING, CAULKING, INTERIOR SHADES,
 AND IF HISTORICLLY APPROPRIATE, BLINDS
 AND AWNINGS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026