Plan Review Notes
Plan Review Notes For Permit 03120591
Permit Number 03120591
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT A2.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 WITH ALL SUBSEC-
 TIONS FOR EXISTING ROOF. SHOW 1/2 AREA
 OF ALL VERTICAL WALLS & AREA OF ROOFS
 THAT DRAIN DOWN TO THE ROOF FROM ABOVE.
 INDICATE SIZE OF DOWNSPOUTS & SUBMIT A
 DETAIL FOR ALL OPENINGS IN THE PARAPET
 WALLS SHOWING ALL DIMENTIONS. IF PRIMARY
 AND SECONDARY DRAINS DRAIN THROUGH THE
 SAME OPENING, THE OPENING SHALL BE SIZED
 ACCORDINGLY.
 2) SHT P0.1 GENERAL SPECIFICATIONS #2, &
 PLUMBING LEGEND. AIR CHAMBERS ARE NOT
 APPROVED, DELETE FROM PLANS. 604.9
 3) SHT P0.1 DEMO NOTES: ALL CAPPED AND
 ABANDONED PLUMBING LINES SHALL BE INSP-
 ECTED PRIOR TO COVERING.
 4) SHT P2.1 HUB DRAIN IN SPRINKLER CON-
 TROL ROOM #103 SHOWS 1" CONDENSATE
 DRAINING INTO IT. CONDENSATE SHALL DRAIN
 SEPARATELY OUTSIDE OF THE BLDG. AND TIE
 INTO STORM, A CATCH BASIN, OR A DRY WELL
 A RELIEF VENT IS REQUIRED AS CONDENSATE
 EXITS THE BLDG. SAFE WASTE'S ARE NOT
 APPROVED. SECTION 90-125(5) CITY CODE.
 5) GREASE INTERCEPTOR SHALL BE SIZED BY
 UTILITY DEPT. CONTACT RODNEY COMPO, EN-
 VIRONMENTAL COMPLIANCE, INDUSTRIAL PRE-
 TREATMENT WASTE ORD. 2938-96 (561) 837-
 4074.
 6) SHT P5.3 ALL WATER RISER DIAGRAMS,
 AIR CHAMBERS ARE NOT APPROVED, DELETE
 FROM RISERS. WATER HAMMER ARRESTORS RE-
 QUIRED BY 604.9 (ICE MAKERS/WASHMACHINES
 & DISH WASHERS), SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AT THE TOP OF THE DROPS.
 7) SHTS P5.3 & P0.1 SUBMIT MANUF. SPECS.
 SHEETS FOR TANKLESS WATER HEATER. MUST
 SHOW LISTING FOR W/H.
 8) IF PRACTICING THROUGH A DULY AUTHOR-
 IZED ENGINEERING BUSINESS, ENGINEERS
 SHALL INDICATE THEIR CERTIFICATE OF
 AUTHORIZATION ON THE TITLE BLOCK OF EACH
 SHEET. 61G15-23.002(2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]