| Date |
Text |
| 2003-12-29 00:00:00 | DENIED: |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | 1.OUTSIDE AIR CALCULATIONS PER 2001 |
| | FBC(M) TABLE 403.3. |
| | |
| | 2.INDICATE LOCATION OF THE OUTSIDE AIR |
| | DUCT TO THE AHU'S LOCATED ON THE 2ND |
| | FLOOR. |
| | |
| | 3.PROVIDE MINIMUM VENTILATION REQUIRE- |
| | MENTS FOR THE 1ST FLOOR PER 403.4.1. |
| | |
| | 4.PLAN SHEET M2.1 INDICATES THE SUPPLY |
| | AND RETURN DUCTS FROM RTU-1 PENETRATING |
| | THROUGH A STAIR WELL ENCLOSURE.PER |
| | 2001 FBC 1006.1.3.1, DUCTWORK IS NOT |
| | ALLOWED TO PENETRATE A STAIRWAY |
| | ENCLOSURE, PLEASE CLARIFY. |
| | |
| | 5.PLAN SHEET M2.1 DUCTWORK FROM RTU-1, |
| | DUCTS PENETRATING ONLY ONE FLOOR OF A |
| | BUILDING REQUIRING THE PROTECTION OF |
| | VERTICAL OPENINGS SHALL HAVE A FIRE |
| | DAMPER.DUCTS THAT PENETRATE MORE THAN |
| | ONE FLOOR SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE PER 2001 FBC(M) 607.1.2 #3 & |
| | 607.4 RESPECTIVELY. |
| | |
| | 6.PLAN SHEET M6.1 CONDENSING UNIT |
| | DETAIL, HEIGHT REQUIREMENT FROM THE |
| | ROOF SURFACE TO THE BOTTOM OF THE |
| | SUPPORT RAIL SHALL COMPLY WITH 2001 FBC |
| | 1511.7. |
| | |
| | 7.REFRIGERANT PIPING SHALL COMPLY WITH |
| | 15-1992 SUB SECTION 11.12.3(B) & 11.12.4 |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |